Plan Review Notes For Permit 22110559 |
Permit Number |
22110559 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-17 09:29:01 | FUEL GAS PLAN AUDIT | | PERMIT- 22110559 | | 1/17/2023 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | AUDIT RESULTS: | | | | 1) GAS RISER: PLEASE CHANGE THE TIKI TORCH LABELS TO | | FIRE BOWLS- SEC. 107.2.1 WPB. | | | | 2) GAS RISER: SHOW THE SIZE OF THE MAIN SUPPLY PIPE | | FROM THE METER TO THE PE RISER- TABLE 402.4(5) FBC RES. | | | | 3) GAS RISER: THE PIPE LABEL FOR THE 22 FT. RUN TO THE | | DRYER IS NOT LEGIBLE- SEC. 107.2.1 WPB. | | | | 4) GAS PLAN: SHOW THE MEANS OF PROVIDING COMBUSTION AIR | | TO THE INTERIOR TANKLESS WATER HEATER, THE RANGE, AND | | THE DRYER- SEE SECS. G2407.1, G2439.1, G2447.1, & | | G2448.1 FBC RES. IF USING INDOOR AIR PER SEC. G2407.5 | | PLEASE SHOW CALCULATIONS. | | | | 5) GAS PLAN: PROVIDE GAS VENTING DETAILS FOR THE | | INTERIOR WATER HEATER. SHOW THE TYPE AND SIZE OF VENT | | FLUE, VENT RUN AND TERMINATION LOCATION- SECS. G2427.1 | | & G2439.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | 2022-12-19 15:40:51 | NO GAS REVIEW PENDING PP AFFIDAVIT RESUBMITTAL. |
|