Plan Review Notes For Permit 22110520 |
Permit Number |
22110520 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-05 13:47:25 | BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22110520 | | 475 CLAREMORE DR. | | | | 1- NEED TO PROVIDE SIGNED AND SEALED STRUCTURAL PLANS | | SHOWING THE WIND DESIGN DATA REQUIRED BY SEC. 1603.1.4 | | FBC-BUILDING. SEC. 107.2.1.2 CITY AMENDMENTS. | | | | 2- NEED TO PROVIDE COMPLETE SIGNED AND SEALED | | STRUCTURAL PLANS/SECTIONS/FOUNDATION FOR THE | | CONSTRUCTION OF THE TWO PERGOLAS. DESIGN TO COMPLY WITH | | SEC. 1609.1 FBC-BUILDING. SEC. 107.2.1.2 CITY | | AMENDMENTS. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|