Plan Review Notes
Plan Review Notes For Permit 22110471
Permit Number 22110471
Review Stop B
Sequence Number 4
Notes
Date Text
2023-06-26 11:00:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, E1 STATES THAT WIND LOAD CALCS AND
 STRUCTURAL DETAILS ARE TO BE SUBMITTED. NOTE THAT THE
 DESIGN CRITERIA IS 175MPH PER E1.
  
 THE ENGINEERING PREPARED BY ESRA HASANBAS PERSELLIN, PE
 IS NOT DIGITALLY SIGNED. PLEASE UPLOAD A DIGITALLY OR
 ELECTRONICALLY SIGNED DOCUMENT. IF MR. PERSELLIN DOES
 NOT HAVE A DIGITAL OR ELECTRONIC SIGNATURE, A PAPER
 ORIGINAL MAY BE SUBMITTED TO THE FRONT COUNTER.
  
 THE POLE WAS DESIGNED TO 170MPH, SHEET E1 REQUIRES
 175MPH. EITHER REVISE E1 TO STATE 170MPH OR REVISE POLE
 ENGINEERING TO BE 175MPH.
  
  
  