2023-04-04 14:09:23 | 3RD REVIEW FMC |
| PERMIT: |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS 5600 SQUARE FOOT PET RESORT WILL REQUIRE |
| OUTDOOR AIR FOR 56 PEOPLE AND THE SPACE FOR A TOTAL OF |
| 1,428 CFM???S. IT WILL ALSO REQUIRE A TOTAL EXHAUST OF |
| 5,040 CFM???S BASED ON WHAT WAS SUBMITTED. SHEET M-2 |
| INDICATES IN THE EXHAUST FAN SCHEDULE THAT EACH EXHAUST |
| FAN IS 110 CFM. THE DRAWING SEEMS TO INDICATE THAT EACH |
| FAN IS 330 CFM. THE DRAWING AND SCHEDULE WILL NEED TO |
| MATCH. FMC TABLE 403.3.1.1 |
| |
| 2) THE EXISTING RTUS INDICATE THAT 4 UNITS HAVE A |
| SUPPLY AIR OF 2000 CFM???S AND 350 CFMS OF OUTDOOR AIR. |
| THE ONE RTU HAS 1600 CFMS OF SUPPLY WITH 250 CFMS OF |
| OUTDOOR AIR. THIS A TOTAL OF 1650 CFM???S OF OUTDOOR |
| AIR ENTERING THE BUILDING WITH A TOTAL OF 5600CFM OF |
| EXHAUST AIR INCLUDING THE BATHROOMS LEAVING THIS |
| BUILDING. PLEASE SHOW HOW THIS DESIGN WILL BE BALANCED. |
| FMC 403.3.1.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |