2023-02-28 11:46:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22110423 |
| ADD: 2617 N AUSTRALIAN AVE. |
| CONT: MASTER CONTRACTORS |
| TEL: 561-712-8898 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. DEC. 28TH/ 2022 |
| ACTION: DENIED |
| |
| 1) COVERSHEET: |
| 1A) COMPLIED. |
| 1B) SEMI-COMPLIED. CHANGED TO EXPOSURE D BUT DID NOT |
| CHANGE PRESSURES ROOF AND WALL COMPONENTS AND CLADDING |
| ( AS PLAN STATEMENT WORST CASE ALL OPENINGS) WALL ZONE |
| 5 AND ROOF ZONES 1, 2, & 3. |
| |
| 2) COMPLIED. |
| 3) SHEET A-1 CONSTRUCTION FLOOR PLAN. SHOWS NEW |
| EXTERIOR DOOR OPENINGS AND DOORS. |
| 3A)SEMI-COMPLIED, MISSING THE PRODUCT APPROVAL FOR THE |
| NEW OPENING EAST SIDE, DOOR SIDELIGHTS (WINDOWS & |
| VERTICAL MULLION, BETWEEN WINDOW & DOOR JAMB NEW DOUBLE |
| GLASS DOOR SYSTEM. ) |
| 1ST ROUND OF COMMENTS. COMPONENTS & CLADDING. PLEASE |
| SUBMIT THE COMPONENTS AND CLADDING PRODUCT APPROVALS. |
| 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS |
| (B) DOOR SIDELIGHT WINDOWS |
| |
| 3B) SEMI-COMPLIED, NEED WINDOW AND MULLION REPORTS. W. |
| P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20 |
| SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP DRAWING |
| STAMP OF APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 3C) SEMI-COMPLIED. NEED WINDOW AND MULLION REPORTS. |
| IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER???S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 3D)(1) SEMI-COMPLIED. PLEASE PROVIDE THE WIDTH OF THE |
| EXISTING SIDEWALK. EXISTING ADA RAMP DOOR TO HOTEL |
| STAFF ENTRANCE ONLY NEEDS TO SHOW COMPLIANCE WITH |
| 2020-ACCESSIBILITY CODE FIGURE 404.2.1 FIGURE |
| ( E ). |
| |
| 3D)(2) NEW COMMENT. EXISTING DOOR WEST SIDE OF BUILDING |
| AT EXISTING ADA RAMP TO STAFF TRAINING ROOM IS MISSING |
| THE REQUIRED MANEUVERING CLEARANCE LETCH SIDE OF DOOR. |
| ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. DOORS. |
| MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| LATCH SIDE FOR SIDE CLEARANCE. |
| FIGURE 404.2.1(A) |
| |
| 1ST ROUND OF COMMENTS. THE FLOOR PLAN SHOWS FROM THE |
| NEW LOBBY THERE IS A SERIES OF EXISTING STAIRS THAT |
| EITHER DROP OR ARE RAISED TO THE HOTEL AERA. THE FLOOR |
| PLAN DOES NOT SHOW COMPLIANCE WITH VERTICAL |
| ACCESSIBILITY REQUIREMENTS. PLEASE REVIEW SECTION |
| 201.1.1 VERTICAL ACCESSIBILITY & SECTION 408 FOR LULA |
| LIFT, LIMITED USE LIMITED APPLICATION. |
| |
| 3E) COMPLIED. BREAKROOM DOOR. |
| |
| 3F) COMPLIED. INFILL HOTEL & STAFF TRAINING ROOM. |
| |
| 3G)(1) COMPLIED. THE NEW BREAK ROOM SINK AND CABINETS . |
| 3G)(2) COMPLIED. 606.2 CLEAR FLOOR SPACE |
| |
| 3H) COMPLIED DOOR. |
| |
| 3I) COMPLIED. THE LOBBY RECEPTION DESK. |
| |
| 3J) COMPLIED. DRINKING FOUNTAIN. NO FEWER THAN TWO |
| DRINKING FOUNTAINS. |
| |
| 3K) 2ND REQUEST. DRINKING FOUNTAINS PROTRUDING OBJECTS |
| 307.2 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING |
| EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES |
| ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES |
| HORIZONTALLY INTO THE CIRCULATION PATH. |
| |
| 3L) COMPLIED. DRINKING FOUNTAIN 602.2 CLEAR FLOOR SPACE |
| |
| 3M) COMPLIED. POUT OUTLETS/ DRINKING FOUNTAINS |
| |
| |
| |
| 4)COMPLIED. SHEET A-3 BATHROOM ACCESSIBILITY DETAILS: |
| |
| 5) CMPLIED. |
| |
| 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |