2022-12-14 15:48:381ST REVIEW FMC
 PERMIT: 22110423
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE OUTDOOR AIR CALCULATION
 AND EXHAUST FOR EACH SPACE IN THIS PROJECT ACCORDING TO
 THE OCCUPANCY CLASSIFICATION AND OCCUPANT DENSITY FROM
 FMC TABLE 403.3.1.1. I SEE ON SHEET M-2 THE FRESH AIR
 CALCULATIONS ARE SHOWN SHOWING THE ENTIRE SQUARE
 FOOTAGE AS PET AREA. THIS IS OK BUT THE NEW EXHAUST
 EQUIPMENT SCHEDULE ONLY SHOWS EXHAUST IN CERTAIN ROOMS.
 THE CALCULATIONS SHOULD SHOW THE ENTIRE STORY OF THIS
 SPACE. ACCORDING TO FOOT NOTE B OF TABLE 403.3.1.1
 B. MECHANICAL EXHAUST REQUIRED AND THE RECIRCULATION OF
 AIR FROM SUCH SPACES IS PROHIBITED. RECIRCULATION OF
 AIR THAT IS CONTAINED COMPLETELY WITHIN SUCH SPACES
 SHALL NOT BE PROHIBITED (SEE SECTION 403.2.1, ITEM 3).
 IF A SPACE IS TO HAVE PETS IN IT, EXHAUST WOULD BE
 REQUIRED AND RECIRCULATION OF AIR TO OTHER AREAS WOULD
 NOT BE ALLOWED. IF THE ENTIRE 5600 SQUARE FEET OF AREA
 IS TO BE USE AS PET AREA THEN THE EXHAUST AIR WOULD
 INCREASE.
  
 2) PLEASE SHOW THE MECHANICAL DESIGN FOR THIS TENANT
 CAN SUPPORT THE REQUIRED OUTDOOR AND EXHAUST AIR FOR
 THIS NEW TENANT. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  