Plan Review Notes For Permit 22110423 |
Permit Number |
22110423 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-05 10:37:09 | FIRE PROVISO COMMENTS: | | | | (1) DOOR LOCKS, 7.2.1.5 LOCKS, LATCHES, AND ALARM | | DEVICES. | | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | OCCUPIED. | | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER | | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE | | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | OPERATION FROM THE EGRESS SIDE. | | | | (2) PORTABLE FIRE EXTINGUISHERS OF THE APPROPRIATE | | QUANTITY, SIZE AND TYPE FOR THE HAZARD SHALL BE | | PROVIDED WITHIN 75 FT. OF TRAVEL DISTANCE FROM ANY | | POINT INSIDE THE BUILDING. NFPA 38.3.5 | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|