2023-01-25 16:35:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. FBC EB 702.5, PROVIDE INFORMATION REGARDING THE
 OPENING SIZE FOR THE EXISTING WINDOWS, OPENING SIZE FOR
 PROPOSED WINDOWS (HORIZONTAL ROLLER WINDOWS IN
 BEDROOMS).
  
 2ND REVIEW - PROVIDE THE CLEAR OPENING DIMENSIONS FROM
 THE MANUFACTURER. THE INFORMATION REQUESTED WAS NOT
 PROVIDED. A PHOTOGRAPH THAT DOES NOT RESPOND TO THE
 COMMENT WAS UPLOADED. NOTE THAT A 48" WIDE HORIZONTAL
 WINDOW IS PROPOSED AND NOTED AS EGRESS. IT APPEARS THAT
 COMPLIANT EGRESS WINDOWS EXIST IN THESE LOCATIONS (3
 BEDROOMS). PROVIDE DATA FROM THE MANUFACTURER TO SHOW
 THAT THE 48" HORIZONTAL ROLLER WINDOWS MEET EGRESS
 REQUIREMENTS.
  
  