Plan Review Notes For Permit 22110394 |
Permit Number |
22110394 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-01-25 16:35:42 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 1. FBC EB 702.5, PROVIDE INFORMATION REGARDING THE | | OPENING SIZE FOR THE EXISTING WINDOWS, OPENING SIZE FOR | | PROPOSED WINDOWS (HORIZONTAL ROLLER WINDOWS IN | | BEDROOMS). | | | | 2ND REVIEW - PROVIDE THE CLEAR OPENING DIMENSIONS FROM | | THE MANUFACTURER. THE INFORMATION REQUESTED WAS NOT | | PROVIDED. A PHOTOGRAPH THAT DOES NOT RESPOND TO THE | | COMMENT WAS UPLOADED. NOTE THAT A 48" WIDE HORIZONTAL | | WINDOW IS PROPOSED AND NOTED AS EGRESS. IT APPEARS THAT | | COMPLIANT EGRESS WINDOWS EXIST IN THESE LOCATIONS (3 | | BEDROOMS). PROVIDE DATA FROM THE MANUFACTURER TO SHOW | | THAT THE 48" HORIZONTAL ROLLER WINDOWS MEET EGRESS | | REQUIREMENTS. | | | | |
|