Plan Review Notes For Permit 22110319 |
Permit Number |
22110319 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-18 21:32:24 | 1. HORIZONTAL ROLLER WINDOW IN OPENING 9 APPEARS TO LIE | | IN WALL ZONE 5, AND IF SO DOES NOT MEET REQUIRED DESIGN | | PRESSURES. PLEASE SUBMIT COMPLIANT FENESTRATION, OR | | VERIFICATION LETTER WITH MEASURMENT FROM CORNER. FBC | | 107.2 2. 2. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A | | NOTE TO THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R | | 703.4 OR FBC B 1405.4. |
|