2022-11-14 13:58:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION ON THE PERMIT APPLICATION |
| OFSOUND PROOFT FOR NEW FLOORING; HOWEVER, THERE IS NO |
| INDICATION OF THE NEW FLOOR PRODUCT/MATERIAL. |
| |
| FFLOORING IS MANUFACTURED AROUND THE WORLD AND NOT ALL |
| ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE |
| PROPOSED NEW FLOORING INDICATING THE FIRE BEHAVIOR |
| RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| 2) THERE IS A FLOOR PLAN SUBMITTED; HOWEVER, THERE IS |
| NO INDICATION OF THE AREAS OF THE NEW FLOOR. |
| |
| FOR THE OFFICIAL RECORD PLEASE INDIOCATE WHERE THE NEW |
| FLOORING WILL BE LOCATED. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |