2023-02-07 14:30:51 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 22110296 |
| 2/7/23 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER: THE 1/2-INCH GALVANIZED PIPE TO THE |
| GENERATOR SHALL BE INCREASED IN SIZE TO MINIMUM |
| 3/4-INCH- TABLE G2413.4(2) FBC RES. |
| |
| 2) GAS RISER: SHOW THE TYPE AND SIZE OF PIPE FROM THE |
| 1-INCH PE TO THE EXISTING TANKLESS WATER HEATER- SEC. |
| G2413.3 FBC RES. |
| |
| 3) GAS RISER: PLEASE SHOW THE EHD OF THE CSST PIPING- |
| SEC. G2413.3 FBC RES. |
| |
| 4) SHEET P1.0: THE MARKED-UP PLAN WILL REQUIRE THE |
| DIGITAL SIGNATURE AND SEAL OF THE REGISTERED ARCHITECT- |
| FL STATUTE 481.221 AND SEC. 61G1-16.005 FAC. THE |
| CONTRACTOR WHO PUT THE MARKINGS ON THE PLAN MAY SUBMIT |
| HIS OWN FLOOR PLAN SKETCH TO SHOW THE APPLIANCE AND |
| PIPING LOCATIONS- SEC. 107.2.1 WPB. |
| |
| 5) P1.0: THE GENERATOR IS UNDER SEPARATE PERMIT REVIEW |
| HOWEVER PLEASE NOTE THAT THE GENERATOR EXHAUST SHALL BE |
| A MINIMUM OF 10 FT. FROM GRAVITY AND MECHANICAL AIR |
| INTAKES INTO THE BUILDING- R303.5.1 FBC RES. |
| |
| 6) P1.0: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| RANGE PER SEC. G2407.1 FBC RES. PLEASE NOTE A TOTAL OF |
| 3475 CU. FT OF OPEN AIR IS REQUIRED FOR THE 69,500 BTU |
| RANGE IF USING THE INDOOR VOLUME OF THE SPACE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |