2022-11-17 10:21:11 | FIRE PROVISO COMMENTS: | | | | (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | FIRE WATCH. | | | | (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE | | DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION | | INCLUDING PAINTING. | | | | (4) ANY WORK OR MODIFICATIONS, ADDITIONS, ON ANY LIFE | | SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM) SHALL | | BE PERFORMED BY PROPERLY LICENSED CONTRACTORS UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|