2023-02-10 12:52:04FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 220
 2, PROVIDE INFORMATION OF SERVICE, INCLUDING PROTECTION
 AND GROUNDED CONDUCTOR. NEC 230, 240, 250.102(C)
 2. PROVIDE INFORMATION OF THE PANEL SCHEDULE. NEC
 408.4(A)
 3. PROVIDE INFORMATION OF THE NEW FEEDERS, CIRCUITS AND
 EGC TO BE INSTALLED. NEC 220, 250.122
 4. RECEPTACLES INSTALLED IN GARAGES MUST PROVIDE GFCI
 PROTECTION. NEC 208(A)(2)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  