2023-02-13 15:17:50 | 1ST BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| 1. PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). ELEVATION CERTIFICATES ARE REQUIRED. |
| SEE COMMENTS UNDER NFIP REVIEW. |
| |
| 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| |
| 3.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT |
| APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED |
| WINDOW AND OVERHEAD DOOR (OHD). |
| FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 4.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE |
| SPEC. SHEET OF A FLUID APPLIED MEMBRANE. |
| R703.4 |
| |
| 5.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7. |
| |
| 6. IF SMART VENTS ARE UTILIZED FOR FLOOD OPENINGS, |
| PROVIDE THE FLORIDA PRODUCT APPROVALS AND THE ICC-ES |
| REPORT. IDENTIFY WHICH VENTS WILL BE INSTALLED. LOCATE |
| TYPE OF VENTS WITH MODEL NUMBER ON FLOOR PLAN. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |