Plan Review Notes For Permit 22110058 |
Permit Number |
22110058 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-11-17 12:48:31 | 1) SHOW HOW THE MAKE-UP AIR MEETS THE 10 DEGREES | | REQUIREMENT OF FMC 508.1.1 | | | | 2) PROVIDE HE AIR BALANCE DIAGRAM ACCORDING TO FMC | | 508.1.2 | | | | 3) PROVIDE DETAIL DRAWINGS AND UL LISTING FOR THE | | FIRESTOPPING OF THE FLOOR CEILING PENETRATIONS. FMC | | 607.6.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|