Plan Review Notes
Plan Review Notes For Permit 22110058
Permit Number 22110058
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-17 12:48:311) SHOW HOW THE MAKE-UP AIR MEETS THE 10 DEGREES
 REQUIREMENT OF FMC 508.1.1
  
 2) PROVIDE HE AIR BALANCE DIAGRAM ACCORDING TO FMC
 508.1.2
  
 3) PROVIDE DETAIL DRAWINGS AND UL LISTING FOR THE
 FIRESTOPPING OF THE FLOOR CEILING PENETRATIONS. FMC
 607.6.1
  