2022-12-06 07:02:321ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - PLEASE SHOW THE OVERALL FLOOR
 PLAN AND THE OCCUPANT LOAD. SHOW THAT THE MINIMUM
 FACILITES REQUIRED BY THIS SECTION HAVE BEEN MET.
  
 2. 2017 WPB AMENDS 107.3.5.1.3 PLEASE SHOW A MORE
 COMPREHENSIVE RISER DETAILING WHERE THE DRAINS FOR THE
 DRINKING FOUNTAIN AND EXAM SINK ARE CONNECTING. PLEASE
 NOTE THAT THE LAVATORIES ARE TYPICALLY WET VENTS FOR
 THE WATER CLOSETS, AND ANY FIXTURE THAT IS NOT A
 BATHROOM GROUP FIXTURE MUST DISCHARGE DOWNSTREAM OF THE
 LAST BATHROOM GROUP FIXTURE'S CONNECTION TO THE WET
 VENT SYSTEM.
  
 3. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND
 SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR
 PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE
 DEVICE SHOULD CONFORM TO ASSE 1070.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved