Plan Review Notes
Plan Review Notes For Permit 22110022
Permit Number 22110022
Review Stop P
Sequence Number 2
Notes
Date Text
2023-01-10 07:16:202ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NOT COMPLIED -- THIS COMMENT IS FOR ALL HOT WATER
 DELIVERY, NOT TEMPERED WATER AT PUBLIC HAND WASHING. IT
 SHOULD BE REFLECTED AT THE WATER HEATER DETAIL ON P-3
 AS WELL AS THE ISOMETRICS ON P-2 AND NOTATED ON THE
 FLOOR PLAN ON P-1.
 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
 2. DONE
  
 3. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved