2022-12-08 12:24:39 | ELECTRIC REVIEW FAILED |
| |
| 1) PLEASE INSERT A NOTE IN ELECTRICAL PLANS INDICATING |
| ALL PATIENT CARE SPACES WILL BE PROVIDED WITH AN |
| EFFECTIVE GROUND-FAULT PATH AS REQUIRED PER NEC 517.13 |
| |
| 2) PLEASE PROVIDE CLARITY ON THE ELECTRICAL RISER |
| DIAGRAM IDENTIFYING MAIN DISCONNECTS. IT APPEARS THE |
| LANGUAGE DESCRIBING THESE DISCONNECTS COULD BE |
| CONFUSING. IT IS BELIEVED THE MAIN DISCONNECT IN THE |
| ELECTRIC ROOM IS A MAIN, HOWEVER THE TRANSFER SWITCH |
| OUTSIDE WOULD BE BETTER DESCRIBED AND MARKED AS A |
| GENERATOR TRANSFER SWITCH FOR MAIN SERVICE #1 |
| . |
| 3) HOUSE PANEL ON RISER DIAGRAM DOES NOT INDICATE ANY |
| MAIN OVERCURRENT PROTECTION OR INDICATION OF OTHER MAIN |
| BREAKERS IN ENCLOSURE. PLEASE CORRECT WITH ONE OF THE |
| APPLICABLE NEC REQUIREMENTS BELOW. |
| |
| INDICATE ON ELECTRICAL RISER DIAGRAM, MAIN OVERCURRENT |
| PROTECTION FOR HOUSE PANEL, AND, LABEL AS MAIN 2 OF2. |
| NEC 230.70 (B) AND 215.5. |
| |
| OR |
| |
| INDICATE THE CIRCUIT BREAKERS CONTAINED IN HOUSE PANEL |
| ARE LESS THAN 5, NEC 230.71, AND SERVE AS MAIN |
| DISCONNECTS, MARK THESE BREAKERS ACCORDINGLY AS MAINS |
| 2-5 OF 6 AND 400-AMP MAIN DISCONNECT AS MAIN 1 OF 6 AS |
| APPLICABLE TO THE NUMBER OF MAIN DISCONNECTS. NEC |
| 230.70 (B) |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |