Plan Review Notes For Permit 22101433 |
Permit Number |
22101433 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-21 09:57:45 | FIRE PROVISO COMMENTS: | | | | (1) PROVIDE ADEQUATE CODE COMPLIANT PORTABLE FIRE | | EXTINGUISHER COVERAGE SO THAT TRAVEL DISTANCE TO THE | | NEAREST PORTABLE FIRE EXTINGUISHER DOES NOT EXCEED 75 | | FEET (I.E. LAUNDRY ROOM, COMMUNITY/OFFICE BUILDING). | | | | (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A | | FIRE WATCH. | | | | (4) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE | | ALARM) SHALL BE PROTECTED FROM DAMAGE INCLUDING | | PAINTING, DURING ALL PHASES OF DEMOLITION AND | | CONSTRUCTION. | | | | (5) ANY WORK, CHANGES, MODIFICATIONS, ADDITIONS, | | DELETIONS, ETC. OF ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY | | PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS | | AND SHOP DRAWINGS. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|