Plan Review Notes
Plan Review Notes For Permit 22101430
Permit Number 22101430
Review Stop B
Sequence Number 3
Notes
Date Text
2023-03-21 13:58:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22101430
 ADD: 550, 580 EXECUTIVE CENTER DR.
  
 W. P. B. PERMIT: 22101430
 ADD: 540 EXECUTIVE CENTER DR.
  
 CONT: LEGACY CONSTRUCTION SERVICES, INC.
 TEL: 216-297-2170
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 21ST/2023
 ACTION: DENIED
  
 1) COMPLIED. PERMIT 22101425. SHEET G103 BUILDING CODE
 DATA, LEASING / COMMUNITY OFFICE FLOOR PLAN.
  
  
 2) COMPLIED.
  
 3) COMPLIED. SHEET A900. 2020 FBC-B 1603.1.4 WIND
 DESIGN CRITERIA.
  
 4A) NOTE EITHER ALL PRODUCT APPROVALS ARE REVIEWED OR
 NONE AND SUBMITTED LATER AS NO FEE DEFERRED SUBMITTALS.
 SEMI-COMPLIED. SHEET 540 & 580 FLOOR PLANS. NOTE # 1
 REMOVE AND REPLACE VINYL WINDOWS AND EXTERIOR DOORS.
 NOTE # 5 TO REMOVE & REPLACE ALL EXTERIOR DOORS.
 COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS AND
 CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 PGT PATIO DOORS DID NOT LOAD, WILL NOT OPEN FOR REVIEW
 NO EXTERIOR SWING DOORS WERE SUBMITTED.
 (B) WINDOWS & MULLIONS
 PGT HORIZONTAL ROLLERS NOA-20-0406.01 THE NOA IS NOT
 HIGHLIGHTED AS REQUESTED COMMENT 4F.
 PGT SINGLE HUNG WINDOW NOA 20-0401.03 IS NOT
 HIGHLIGHTED AS REQUESTED COMMENT 4F.
 SHEET A-900 DETAILS 8 & 9 SHOW WINDOWS BUT THEY DO NOT
 STATE IF THEY ARE HORIZONTAL SLIDERS OR 2 SINGLE HUNG
 WINDOWS REQUIRING MULLIONS.
 (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS
 SYSTEMS,
  
 4B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4C) NOTICE ONLY: DELEGATED ENGINEERING. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 4D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4E) 2ND REQUEST, PGT PATIO DOOR PRODUCT APPROVAL DID
 NOT OPEN WILL NEED REVIEW FOR PRESSURES AND SILL
 HEIGHT, FOR POSITIVE PRESSURES.
 1ST ROUND OF COMMENTS. 2020 FBC-B 1709.5.1 HABITAT
 SPACES, WATER INTRUSION. EXTERIOR DOORS AND WINDOWS.
 EXCEPTION # 2. SILL LIMITING FACTOR.
  
 4F) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL
 HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 5) COMPLIED NOT APPLICABLE.
  
 6A) SEMI-COMPLIED. A-900 DOOR SCHEDULE NOW SHOWS METAL
 LOUVER DOOR BUT STILL HAS WOOD FRAME, EITHER METAL
 FRAME OR DRYWALL WITH BEADS AND DRYWALL MUD.
 1ST ROUND OF COMMENTS. THIS COMMENT FOR 540 & 580 ALL
 FLOORS AND UNITS. THE AIR HANDLER/ WATER HEATER CLOSET
 SHEET M-200 SHOWS THE REPLACEMENT OF AIR HANDLER, A
 VERTICAL UNIT W/ WATER HEATER BELOW. SHEET A200 NOTE 7
 STATES TO REPLACE THE WATER HEATER. SHEET A200 DOOR FOR
 THE MECHANICAL CLOSET IS LABELED DOOR TYPE 7. SHEET
 A-900 DOOR AND WINDOW SCHEDULE DOOR TYPE 7 IS A WOOD
 LOUVERED BI-FOLD DOOR. SINCE THERE IS NO DIRECT RETURN,
 THE SPACE WITHIN THE MECHANICAL CLOSET IS CONSIDERED A
 PLENUM, NO COMBUSTIBLES ARE ALLOWED IN A PLENUM. PLEASE
 REVIEW IN THE 2020 FBC-MECHANICAL CODE SECTIONS 602.2
 CONSTRUCTION & 602.2.1 MATERIALS WITHIN PLENUMS. METAL
 BI-FOLD DOORS ARE ACCEPTABLE.
  
 6B) SEMI-COMPLIED. SHEET A-203. THE MECHANICAL CLOSET
 VERTICAL A/C AIR HANDLER AND WATER HEATER TO BE
 REPLACED. DOOR TO MECHANICAL CLOSET IS IDENTIFIED AS
 #8. SHEET A-900 TYPE F IS A WOOD HOLLOW CORE BI-FOLD
 DOOR. SINCE THERE IS NO DIRECT RETURN, THE SPACE WITHIN
 THE MECHANICAL CLOSET IS CONSIDERED A PLENUM, NO
 COMBUSTIBLES ARE ALLOWED IN A PLENUM. PLEASE REVIEW IN
 THE 2020 FBC-MECHANICAL CODE SECTIONS 602.2
 CONSTRUCTION & 602.2.1 MATERIALS WITHIN PLENUMS. METAL
 BI-FOLD DOORS ARE ACCEPTABLE. PLEASE ALSO NOTE THAT THE
 VERTICAL AIR HANDLER WOULD HAVE TO SIT ON A METAL STAND
 NOT WOOD FRAMING.
  
 7) SHEET A-204 COMMON AREA ENLARGED FLOOR PLAN AND
 ELEVATIONS 2020 FBC-ACCESSIBILITY CODE:
  
 7A-B) COMPLIED.
  
 7C) 2ND REQUEST, DRAINPIPES NOT SHOWN, WALL HUNG
 LAVATORY DOES NOT SHOW WASTE PIPES NOR 606.5 EXPOSED
 PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 7D-F) COMPLIED.
  
 8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  