2023-03-17 10:33:26 THESE ARE REPAET COMMENTS FROM AND DRAWINGS TO BE
 RESUBMITTED UNDER
  W. P. B. PERMIT: 22101425
  ADD: 550, 580 EXECUTIVE CENTER DR.
  
  W. P. B. PERMIT: 22101430
  ADD: 540 EXECUTIVE CENTER DR.
  
  CONT: LEGACY CONSTRUCTION SERVICES, INC.
  TEL: 216-297-2170
  E-MAIL: [email protected]
  
  2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
  AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
  ADMINISTRATION
  
  2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
  CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
  SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
  BUILDING CODE, BUILDING.
  
  1ST REVIEW
  DATE: WED. JAN. 25/2023
  ACTION: DENIED
  
  1) COMPLIED. PERMIT 22101425. SHEET G103 BUILDING CODE
  DATA, LEASING / COMMUNITY OFFICE FLOOR PLAN.
  
  
  2) COMPLIED.
  
  3) COMPLIED. SHEET A900. 2020 FBC-B 1603.1.4 WIND
  DESIGN CRITERIA.
  
  4A) SEMI-COMPLIED. IN THE FILE FOLDER THE PGT PATIO
  DOORS DID-NOT LOAD.
  SHEET 540 & 580 FLOOR PLANS. NOTE # 1 REMOVE AND
  REPLACE VINYL WINDOWS AND EXTERIOR DOORS. NOTE # 5 TO
  REMOVE & REPLACE ALL EXTERIOR DOORS. COMPONENTS &
  CLADDING. PLEASE SUBMIT THE COMPONENTS AND CLADDING
  PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF
  OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
  DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
  61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
  OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
  PRODUCT APPROVALS:
  (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
  PGT PATIO DOORS DID NOT LOAD, WILL NOT OPEN FOR REVIEW
  NO EXTERIOR SWING DOORS WERE SUBMITTED.
  (B) WINDOWS & MULLIONS
  PGT HORIZONTAL ROLLERS NOA-20-0406.01 THE NOA IS NOT
  HIGHLIGHTED AS REQUESTED COMMENT 4F.
  PGT SINGLE HUNG WINDOW NOA 20-0401.03 IS NOT
  HIGHLIGHTED AS REQUESTED COMMENT 4F.
  SHEET A-900 DETAILS 8 & 9 SHOW WINDOWS BUT THEY DO NOT
  STATE IF THEY ARE HORIZONTAL SLIDERS OR 2 SINGLE HUNG
  WINDOWS REQUIRING MULLIONS.
  (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS
  SYSTEMS,
  
  4B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
  THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
  ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
  APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL)
 BY
  THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
  JURISDICTIONAL APPROVAL.
  FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
  SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
  SHOP DRAWINGS ETC.
  
  4C) NOTICE ONLY: DELEGATED ENGINEERING. 61G15-30.003
  ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
  (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
  ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
  REVIEW.
  
  4D) NON-COMMENT SUBMITTED COMPONENT & CLADDING PRODUCT
  APPROVALS. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
  PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
  DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
  SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
  TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
  SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS
 SHALL
  HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
  REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
  SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
  DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
  DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
  SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
  RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
  THEM TO THE BUILDING OFFICIAL WITH A NOTATION
  INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
  BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE
 TO
  THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
  ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
  SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
  OFFICIAL.
  
  4E) 2ND REQUEST, PGT PATIO DOOR PRODUCT APPROVAL DID
  NOT OPEN WILL NEED REVIEW FOR PRESSURES AND SILL
  HEIGHT, FOR POSITIVE PRESSURES.
  1ST ROUND OF COMMENTS. 2020 FBC-B 1709.5.1 HABITAT
  SPACES, WATER INTRUSION. EXTERIOR DOORS AND WINDOWS.
  EXCEPTION # 2. SILL LIMITING FACTOR.
  
  4F) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
  IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO
  DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
  BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
  PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL
  HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
  UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
  ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
  SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
  DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
  MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND
  SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
  SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
  USED IN THE TESTS.
  
  5) COMPLIED NOT APPLICABLE.
  
  6A) SEMI-COMPLIED.A-900 DOOR SCHEDULE NOW SHOWS METAL
  LOUVER DOOR BUT STILL HAS WOOD FRAME, EITHER METAL
  FRAME OR DRYWALL WITH BEADS AND DRYWALL MUD.
  1ST ROUND OF COMMENTS. THIS COMMENT FOR 540 & 580 ALL
  FLOORS AND UNITS. THE AIR HANDLER/ WATER HEATER CLOSET
  SHEET M-200 SHOWS THE REPLACEMENT OF AIR HANDLER, A
  VERTICAL UNIT W/ WATER HEATER BELOW. SHEET A200 NOTE 7
  STATES TO REPLACE THE WATER HEATER. SHEET A200 DOOR
 FOR
  THE MECHANICAL CLOSET IS LABELED DOOR TYPE 7. SHEET
  A-900 DOOR AND WINDOW SCHEDULE DOOR TYPE 7 IS A WOOD
  LOUVERED BI-FOLD DOOR. SINCE THERE IS NO DIRECT
 RETURN,
  THE SPACE WITHIN THE MECHANICAL CLOSET IS CONSIDERED A
  PLENUM, NO COMBUSTIBLES ARE ALLOWED IN A PLENUM.
 PLEASE
  REVIEW IN THE 2020 FBC-MECHANICAL CODE SECTIONS 602.2
  CONSTRUCTION & 602.2.1 MATERIALS WITHIN PLENUMS. METAL
  BI-FOLD DOORS ARE ACCEPTABLE.
  
  6B) SHEET A-203. THE MECHANICAL CLOSET VERTICAL A/C
 AIR
  HANDLER AND WATER HEATER TO BE REPLACED. DOOR TO
  MECHANICAL CLOSET IS IDENTIFIED AS #8. SHEET A-900
 TYPE
  F IS A WOOD HOLLOW CORE BI-FOLD DOOR. SINCE THERE IS
 NO
  DIRECT RETURN, THE SPACE WITHIN THE MECHANICAL CLOSET
  IS CONSIDERED A PLENUM, NO COMBUSTIBLES ARE ALLOWED IN
  A PLENUM. PLEASE REVIEW IN THE 2020 FBC-MECHANICAL
 CODE
  SECTIONS 602.2 CONSTRUCTION & 602.2.1 MATERIALS WITHIN
  PLENUMS. METAL BI-FOLD DOORS ARE ACCEPTABLE. PLEASE
  ALSO NOTE THAT THE VERTICAL AIR HANDLER WOULD HAVE TO
  SIT ON A METAL STAND NOT WOOD FRAMING.
  
  7) SHEET A-204 COMMON AREA ENLARGED FLOOR PLAN AND
  ELEVATIONS 2020 FBC-ACCESSIBILITY CODE:
  
  7A) 2ND REQUEST. DETAILS 4 & 10 PLEASE REVIEW TOILET
  PAPER DISPENSERS. 604.7. THE TOILET PAPER DISPENSER
  SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
  TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
  MEASURED TO THE CENTERLINE OF THE DISPENSER.
  
  7B) 2ND REQUEST. THE SIDE GRAB BARS ARE NOT
 DIMENSIONED
  FROM THE CORNER WALL. 2020 FBC-ACCESSIBILITY CODE
  SECTION 604.5.1 THE SIDE WALL GRAB BAR SHALL BE 42
  INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM
 THE
  REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE
 REAR
  WALL.
  
  7C) 2ND REQUEST, DRAINPIPES NOT SHOWN, WALL HUNG
  LAVATORY DOES NOT SHOW WASTE PIPES NOR 606.5 EXPOSED
  PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
  LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
  CONFIGURED TO PROTECT AGAINST CONTACT.
  
  7D) COMPLIED. DETAIL # 12 THE KITCHENETTE SHOWS THE
  HEIGHT TO THE TOP OF THE BACK SPLASH TO BE 2FEET 10
  INCHES, NOT TO THE COUNTERTOP. SINKS> 2020
  FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES
  AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
  HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
  ABOVE THE FINISH FLOOR OR GROUND.
  
  7E)2ND REQUEST. FLOOR PLAN IS MISSING THE REQUIRED
  CLEAR FLOOR SPACE. 606.2 CLEAR FLOOR SPACE. A CLEAR
  FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
  FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
  WITH 306 SHALL BE PROVIDED, SEE EXCEPTIONS ALSO, BUT
  SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
  7F) THE FLOOR PLAN SHOWS A SINGLE DRINKING FOUNTAIN.
  THE 2020 EXISTING BUILDING CODE LEVEL I, LEVEL 2 OR
  LEVEL 3 ALL REFER YOU TO THE 2020 FBC-ACCESSIBILITY
  CODE. FLORIDA ACCESSIBILITY CODE SECTION:
  DISPROPORTIONATE COST 202.4.1. PART OF THE UPGRADES
  WOULD INCLUDE:
  
  7F)(1-2) COMPLIED.
  7F)(3) 2ND REQUEST. 602.2 CLEAR FLOOR SPACE. A CLEAR
  FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
  FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
  WITH 306 SHALL BE PROVIDED.
  
  7F)(4) 2ND REQUEST. SPOUT OUTLETS/ DRINKING FOUNTAINS.
  2017 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
  602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
  FLOOR OR GROUND FOR WHEELCHAIR BOUND
  INDIVIDUALS.
  602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
  BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
  8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
  ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
  THE REVISION MADE, IDENTIFYING THE SHEET OR
  SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
  HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
  ANTICIPATED COOPERATION.
  
  PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
  REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
  REVIEW CYCLE.
  PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
  REVIEW, SUBSEQUENT
  REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
  MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30
 PM
  PART-TIME/ SEMI-RETIRED.
  
  IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I
 GET
  BACK INTO THE OFFICE CALL
  (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
  THANK YOU.
  
  JAMES A. WITMER BN, PX, SFP, CBO
  SENIOR COMMERCIAL COMBINATION PLANS EXAMINER