2023-02-13 11:12:44FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OR SPECIFICATIONS OF NEW
 EQUIPMENT (WATER HEATERS, ELECTRIC AIR HANDLERS, SMOKE
 ALARMS, EXHAUST FAN , ETC). FBC 107.2
 2. PROVIDE INFORMATION OF EXISTING ELECTRICAL PANEL AND
 PROTECTION (INCLUDING PANEL SCHEDULE). NEC 240, 408,
 408.4(A)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  