Date |
Text |
2023-02-13 10:52:11 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22101430 |
| ADD: 540 EXECUTIVE CENTER DR. |
| |
| |
| W. P. B. PERMIT: 22101425 |
| ADD: 550, 580 EXECUTIVE CENTER DR. |
| CONT: LEGACY CONSTRUCTION SERVICES, INC. |
| TEL: 216-297-2170 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JAN. 25/2023 SAME PLAN MON. FEB. 13TH/ |
| 2023 |
| ACTION: DENIED |
| |
| 1) PERMIT 22101425. SHEET G103 BUILDING CODE DATA, |
| LEASING / COMMUNITY OFFICE FLOOR PLAN: |
| |
| 1A) NOTE # 5. LIST FIRE RESISTANCE RATINGS, BUT NONE IS |
| PROVIDED FOR ROOMS SUCH AS FIRE PUMP ROOM, TRASH CHUTE |
| ELEVATOR MACHINE ROOMS, ETC. |
| 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 1B) BUILDING 540 & 580. NOTE # 7. WASTE HANDLING, N/A. |
| PLEASE PROVIDE AN EXPLANATION SINCE THE MASTER PLAN |
| WHEN BUILT SHOWS A 2-HOUR SHAFT FOR TRASH CHUTE, ACCESS |
| ROOM AND THE FIRST FLOOR A TRASH TERMINATION ROOM AS |
| WELL AS ELEVATOR MACHINE ROOM, WHICH ARE ALL MISSING. |
| 713.13.4 OF THE 2020 FBC-BUILDING CODE. |
| |
| 1C) PLEASE NOTE THESE PERMITS ARE FOR THE REMODELING OF |
| THE (2) BUILDINGS ONLY. SEPARATE PERMITS ARE REQUIRED |
| FOR RESURFACING& STRIPING OF THE PARKING LOT, FENCES, |
| AWNINGS, SIGNS, GENERATOR, POOL AND OR DECK INCLUSIVE |
| OF EQUIPMENT IF SAME CONTRACTOR, DUMPSTER ENCLOSURE, |
| IRRIGATION, LANDSCAPE, FIRE SPRINKLERS AND OR FIRE |
| ALARM. |
| |
| 2) PERMIT 22101425. SHEET A-105 WAS LOADED WRONG, THERE |
| IS A BLANK SHEET. 2020 WEST PALM BEACH AMENDMENTS TO |
| THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. |
| CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 3) SHEET A100 540 FLOOR PLAN & A103 580. NOTE # 1 |
| REMOVE AND REPLACE VINYL WINDOWS THROUGH OUT NEW |
| WINDOWS TO MEET HURRICANE REQUIREMENTS. THERE ARE NO |
| STRUCTURAL SHEETS PROVIDING THE FOLLOWING INFORMATION. |
| 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 3.2. RISK CATEGORY. |
| |
| 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| |
| 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 3.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER |
| INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2. |
| SILL LIMITING FACTOR. |
| |
| 4A) SHEET 540 & 580 FLOOR PLANS. NOTE # 1 REMOVE AND |
| REPLACE VINYL WINDOWS AND EXTERIOR DOORS. NOTE # 5 TO |
| REMOVE & REPLACE ALL EXTERIOR DOORS. COMPONENTS & |
| CLADDING. PLEASE SUBMIT THE COMPONENTS AND CLADDING |
| PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS |
| SYSTEMS, |
| |
| 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 4C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 4D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 4E) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER |
| INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2. |
| SILL LIMITING FACTOR. |
| |
| 4F) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 5) SHEET A103- FLOOR PLAN 580 (2) UNITS ARE IN GRAY BUT |
| THERE ARE NO NOTES PLEASE EXPLAIN. 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 6A) THIS COMMENT FOR 540 & 580 ALL FLOORS AND UNITS. |
| THE AIR HANDLER/ WATER HEATER CLOSET SHEET M-200 SHOWS |
| THE REPLACEMENT OF AIR HANDLER, A VERTICAL UNIT W/ |
| WATER HEATER BELOW. SHEET A200 NOTE 7 STATES TO REPLACE |
| THE WATER HEATER. SHEET A200 DOOR FOR THE MECHANICAL |
| CLOSET IS LABELED DOOR TYPE 7. SHEET A-900 DOOR AND |
| WINDOW SCHEDULE DOOR TYPE 7 IS A WOOD LOUVERED BI-FOLD |
| DOOR. SINCE THERE IS NO DIRECT RETURN, THE SPACE WITHIN |
| THE MECHANICAL CLOSET IS CONSIDERED A PLENUM, NO |
| COMBUSTIBLES ARE ALLOWED IN A PLENUM. PLEASE REVIEW IN |
| THE 2020 FBC-MECHANICAL CODE SECTIONS 602.2 |
| CONSTRUCTION & 602.2.1 MATERIALS WITHIN PLENUMS. METAL |
| BI-FOLD DOORS ARE ACCEPTABLE. |
| |
| 6B) SHEET A-203. THE MECHANICAL CLOSET VERTICAL A/C AIR |
| HANDLER AND WATER HEATER TO BE REPLACED. DOOR TO |
| MECHANICAL CLOSET IS IDENTIFIED AS #8. SHEET A-900 TYPE |
| F IS A WOOD HOLLOW CORE BI-FOLD DOOR. SINCE THERE IS NO |
| DIRECT RETURN, THE SPACE WITHIN THE MECHANICAL CLOSET |
| IS CONSIDERED A PLENUM, NO COMBUSTIBLES ARE ALLOWED IN |
| A PLENUM. PLEASE REVIEW IN THE 2020 FBC-MECHANICAL CODE |
| SECTIONS 602.2 CONSTRUCTION & 602.2.1 MATERIALS WITHIN |
| PLENUMS. METAL BI-FOLD DOORS ARE ACCEPTABLE. |
| |
| 7) SHEET A-204 COMMON AREA ENLARGED FLOOR PLAN AND |
| ELEVATIONS 2020 FBC-ACCESSIBILITY CODE: |
| |
| 7A) DETAILS 4 & 10 PLEASE REVIEW TOILET PAPER |
| DISPENSERS. 604.7. THE TOILET PAPER DISPENSER SHALL |
| COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9 |
| INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. |
| |
| 7B) THE SIDE GRAB BARS ARE NOT DIMENSIONED FROM THE |
| CORNER WALL. 2020 FBC-ACCESSIBILITY CODE SECTION |
| 604.5.1 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL |
| AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| |
| 7C) WALL HUNG LAVATORY DOES NOT SHOW WASTE PIPES NOR |
| 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY & |
| DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| CONTACT. |
| |
| 7D) DETAIL # 12 THE KITCHENETTE SHOWS THE HEIGHT TO THE |
| TOP OF THE BACK SPLASH TO BE 2FEET 10 INCHES, NOT TO |
| THE COUNTERTOP. SINKS> 2020 FBC-ACCESSIBILITY CODE |
| SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE |
| INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 7E) FLOOR PLAN IS MISSING THE REQUIRED CLEAR FLOOR |
| SPACE. 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED |
| CLEAR FLOOR SPACE ON THE FLOOR PLAN. |
| |
| 7F) THE FLOOR PLAN SHOWS A SINGLE DRINKING FOUNTAIN. |
| THE 2020 EXISTING BUILDING CODE LEVEL I, LEVEL 2 OR |
| LEVEL 3 ALL REFER YOU TO THE 2020 FBC-ACCESSIBILITY |
| CODE. FLORIDA ACCESSIBILITY CODE SECTION: |
| DISPROPORTIONATE COST 202.4.1. PART OF THE UPGRADES |
| WOULD INCLUDE: |
| |
| 7F)(1) 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM |
| NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE |
| PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 |
| THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY |
| WITH 602.7. |
| |
| 7F)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS |
| 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES |
| AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT |
| PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE |
| CIRCULATION PATH. |
| |
| 7F)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| PROVIDED. |
| |
| 7F)(4)SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND FOR WHEELCHAIR BOUND |
| INDIVIDUALS. |
| 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| |
| 8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT |
| REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |