Plan Review Notes For Permit 22101378 |
Permit Number |
22101378 |
|
Review Stop |
Z |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-05-25 15:28:38 | FAILED | | | | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT | | PERMIT - CITY RIGHTS-OF-WAY (22040938) MUST BE APPROVED | | PRIOR TO THIS PERMIT BEING APPROVED. SOME OF THE | | COMMENTS BELOW ARE INCLUDED ON THE PLACEMENT PERMIT | | REVIEW AS WELL AS WITH THIS PERMIT. | | | | 2) UPDATED REPEAT COMMENT: THE SURVEY SHOWS THE POWER | | POLE THAT WILL SUPPLY THE UNDERGROUND POWER ON PRIVATE | | PROPERTY AND REQUIRING A CROSSING OF THE PRIVATE | | PROPERTY TO REACH THE HANDHOLE AT STA 0+00. IN ORDER | | FOR THE UNDERGROUND ELECTRIC TO CROSS PRIVATE PROPERTY, | | IT MUST BE LOCATED WITHIN A GENERAL UTILITY EASEMENT. | | THE SURVEY DOES NOT SHOW AN EASEMENT AT THIS LOCATION. | | IF THERE IS AN EASEMENT, IT MUST BE SHOWN ON THE SURVEY | | AND THE UNDERGROUND ELECTRIC MUST CLEARLY BE SHOWN IN | | THE EASEMENT. IF NO EASEMENT IS PRESENT, THE | | UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE | | LOCATION. **** REGARDLESS WHO IS PULLING THE POWER, | | SINCE IT IS COMING FROM PRIVATE PROPERTY IT MUST BE IN | | AN EASEMENT AND YOU MUST PROVIDE THIS INFORMATION. | | | | THE POLE HEIGHT AND STYLE MEET CITY REQUIREMENTS. THE | | POLE COLOR AT THIS LOCATION IS CORRECTLY SHOWN AS | | RAL/RAYCAP 7042 TRAFFIC GREY A. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | | | |
|