Plan Review Notes
Plan Review Notes For Permit 22101378
Permit Number 22101378
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-12-19 16:33:36FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (22040938) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. SOME OF THE
 COMMENTS BELOW ARE INCLUDED ON THE PLACEMENT PERMIT
 REVIEW AS WELL AS WITH THIS PERMIT.
  
 2) NO SURVEY WAS PROVIDED WITH THIS PERMIT. PLEASE
 INCLUDE THE SURVEY (AND OTHER RELEVANT PLANS) INCLUDED
 WITH THE WCF PERMIT.
  
 3) THE SURVEY PROVIDED WITH THE WCF PERMIT SHOWS THE
 POWER POLE THAT WILL SUPPLY THE UNDERGROUND POWER ON
 PRIVATE PROPERTY AND REQUIRING A CROSSING OF THE
 PRIVATE PROPERTY TO REACH THE HANDHOLE AT STA 0+00. IN
 ORDER FOR THE UNDERGROUND ELECTRIC TO CROSS PRIVATE
 PROPERTY, IT MUST BE LOCATED WITHIN A GENERAL UTILITY
 EASEMENT. THE SURVEY DOES NOT SHOW AN EASEMENT AT THIS
 LOCATION. IF THERE IS AN EASEMENT, IT MUST BE SHOWN ON
 THE SURVEY AND THE UNDERGROUND ELECTRIC MUST CLEARLY BE
 SHOWN IN THE EASEMENT. IF NO EASEMENT IS PRESENT, THE
 UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE
 LOCATION.
  
 4) THE SURVEY PROVIDED WITH THE WCF PERMIT SHOWS THE
 FULL LENGTH OF THE POWER ROUTE, TO INCLUDE THE
 HANDHOLES AND BORE PITS, IS LOCATED WITHIN THE
 RIGHT-OF-WAY, HOWEVER, THE LOCATION OF THE GAS LINE AT
 STA 0+00 IS NOT SHOWN AT THE SAME LOCATION ON THE
 SURVEY AND SHEET E101. BASED ON THE SURVEY, THERE IS A
 DIRECT CONFLICT WITH THE HANDHOLE AND ITS EXCAVATION
 AND THE GAS LINE. YOU NEED TO PROVIDE VERIFICATION FROM
 FPU THAT THEY DO NOT OBJECT TO THE PROPOSED
 INSTALLATION LOCATION OF YOUR FACILITIES.
  
 5) THE LAT/LON FOR THE POLE ON THE SURVEY AND SITE PLAN
 IS SHOWN AS THE HANDHOLE LOCATION ON THE POWER ROUTE
 PLAN. PLEASE ENSURE THAT ALL PLANS ARE LABELED
 CORRECTLY.
  
 6) THE NEWLY UPLOADED SHEET E201 DOES NOT SHOW A POLE
 THAT MEETS THE CITY'S STEALTH REQUIREMENTS. THE
 ORIGINAL SUBMITTAL SHOWED A COMPLIANT POLE DESIGN.
 SHEETS A201 AND A502 PROVIDED WITH THE WCF PERMIT SHOW
 A COMPLIANT POLE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  