2022-12-19 16:33:36 | FAILED |
| |
| 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| PERMIT - CITY RIGHTS-OF-WAY (22040938) MUST BE APPROVED |
| PRIOR TO THIS PERMIT BEING APPROVED. SOME OF THE |
| COMMENTS BELOW ARE INCLUDED ON THE PLACEMENT PERMIT |
| REVIEW AS WELL AS WITH THIS PERMIT. |
| |
| 2) NO SURVEY WAS PROVIDED WITH THIS PERMIT. PLEASE |
| INCLUDE THE SURVEY (AND OTHER RELEVANT PLANS) INCLUDED |
| WITH THE WCF PERMIT. |
| |
| 3) THE SURVEY PROVIDED WITH THE WCF PERMIT SHOWS THE |
| POWER POLE THAT WILL SUPPLY THE UNDERGROUND POWER ON |
| PRIVATE PROPERTY AND REQUIRING A CROSSING OF THE |
| PRIVATE PROPERTY TO REACH THE HANDHOLE AT STA 0+00. IN |
| ORDER FOR THE UNDERGROUND ELECTRIC TO CROSS PRIVATE |
| PROPERTY, IT MUST BE LOCATED WITHIN A GENERAL UTILITY |
| EASEMENT. THE SURVEY DOES NOT SHOW AN EASEMENT AT THIS |
| LOCATION. IF THERE IS AN EASEMENT, IT MUST BE SHOWN ON |
| THE SURVEY AND THE UNDERGROUND ELECTRIC MUST CLEARLY BE |
| SHOWN IN THE EASEMENT. IF NO EASEMENT IS PRESENT, THE |
| UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE |
| LOCATION. |
| |
| 4) THE SURVEY PROVIDED WITH THE WCF PERMIT SHOWS THE |
| FULL LENGTH OF THE POWER ROUTE, TO INCLUDE THE |
| HANDHOLES AND BORE PITS, IS LOCATED WITHIN THE |
| RIGHT-OF-WAY, HOWEVER, THE LOCATION OF THE GAS LINE AT |
| STA 0+00 IS NOT SHOWN AT THE SAME LOCATION ON THE |
| SURVEY AND SHEET E101. BASED ON THE SURVEY, THERE IS A |
| DIRECT CONFLICT WITH THE HANDHOLE AND ITS EXCAVATION |
| AND THE GAS LINE. YOU NEED TO PROVIDE VERIFICATION FROM |
| FPU THAT THEY DO NOT OBJECT TO THE PROPOSED |
| INSTALLATION LOCATION OF YOUR FACILITIES. |
| |
| 5) THE LAT/LON FOR THE POLE ON THE SURVEY AND SITE PLAN |
| IS SHOWN AS THE HANDHOLE LOCATION ON THE POWER ROUTE |
| PLAN. PLEASE ENSURE THAT ALL PLANS ARE LABELED |
| CORRECTLY. |
| |
| 6) THE NEWLY UPLOADED SHEET E201 DOES NOT SHOW A POLE |
| THAT MEETS THE CITY'S STEALTH REQUIREMENTS. THE |
| ORIGINAL SUBMITTAL SHOWED A COMPLIANT POLE DESIGN. |
| SHEETS A201 AND A502 PROVIDED WITH THE WCF PERMIT SHOW |
| A COMPLIANT POLE. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |
| |