2022-11-30 15:06:16ELECTRIC REVIEW FAILED
 1) ELECTRIC PANEL SHOWN IS LOCATED IN A NICHE THAT
 CONTAINS A CABINET. IT APPEARS THIS WILL NOT COMPLY
 WITH NEC 110.26 FOR CLEARANCE AROUND ELECTRIC EQIPMENT
 WHICH REQUIRES 30" OF WIDTH, 36" CLEARSPACE IN FRONT OF
 EQUIPMENT AND 6'6" HEAD ROOM. PLEASE CORRECT AS
 APPLICABLE
 2) PLAN DETAILS LIGHT FIXTURE ABOVE MASTER BATH TUB.
 PLEASE DETAIL HOW THIS WILL COMPLY WITH NEC 410-8
 LUMINAIRS INSTALLED IN TUB OR SHOWER AREAS.
 3) PLEASE DETAIL LOCATION OF NEW CAR CHARGING OUTLET ON
 ELECTRIC PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  