2022-12-14 10:09:29RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22101335
 4451 LAKE LUCERNE CIR
  
 1- OPENINGS #2 AND #4 WITH CLEAR STORM PANELS:
 A)SHUTTER SPAN IS INCORRECT. SHUTTER SPAN CAN NOT BE
 THE SAME SIZE AS THE OPENING. SHUTTER SPAN IS
 DETERMINED BY THE OPENING SIZE AND MINIMUM EDGE
 DISTANCE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)BASED ON THE EDGE DISTANCE SPECIFIED ON THE
 INSTALLATION SCHEDULE, ANCHOR SPACING AT THE BOTTOM
 SUBSTRATE (CONCRETE BLOCK) IS INCORRECT. REVISE AS
 REQUIRED.
 ALSO, KEEP IN MIND SHAPE AND SIZE OF STORM PANEL.
 ANCHOR SPACING NEEDS TO BE IN MULTIPLES OF 6. SEC.
 107.2.1 CITY AMENDMENTS.
 NOTE: 1/4" ITW TAPCON REQUIRES 2" MIN. EDGE DISTANCE.
  
 NOTE: KEEP IN MIND EDGE DISTANCE EXCLUDES STUCCO
 FINISH.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER