Plan Review Notes For Permit 22101335 |
Permit Number |
22101335 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-14 10:09:29 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22101335 | | 4451 LAKE LUCERNE CIR | | | | 1- OPENINGS #2 AND #4 WITH CLEAR STORM PANELS: | | A)SHUTTER SPAN IS INCORRECT. SHUTTER SPAN CAN NOT BE | | THE SAME SIZE AS THE OPENING. SHUTTER SPAN IS | | DETERMINED BY THE OPENING SIZE AND MINIMUM EDGE | | DISTANCE. REVISE AS REQUIRED. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | B)BASED ON THE EDGE DISTANCE SPECIFIED ON THE | | INSTALLATION SCHEDULE, ANCHOR SPACING AT THE BOTTOM | | SUBSTRATE (CONCRETE BLOCK) IS INCORRECT. REVISE AS | | REQUIRED. | | ALSO, KEEP IN MIND SHAPE AND SIZE OF STORM PANEL. | | ANCHOR SPACING NEEDS TO BE IN MULTIPLES OF 6. SEC. | | 107.2.1 CITY AMENDMENTS. | | NOTE: 1/4" ITW TAPCON REQUIRES 2" MIN. EDGE DISTANCE. | | | | NOTE: KEEP IN MIND EDGE DISTANCE EXCLUDES STUCCO | | FINISH. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|