Plan Review Notes For Permit 22101229 |
Permit Number |
22101229 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-02-17 15:47:54 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE PANEL SCHEDULE FOR 200 AMP EXISTING BREAKER | | PANEL. NEC 408.4(A) | | 2. REVIEW LOAD CALCUALTION (ATTENTION TO A/C UNITS | | LOADS). NEC 220.82(B) | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|