Plan Review Notes
Plan Review Notes For Permit 22101229
Permit Number 22101229
Review Stop E
Sequence Number 2
Notes
Date Text
2023-02-17 15:47:54FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE PANEL SCHEDULE FOR 200 AMP EXISTING BREAKER
 PANEL. NEC 408.4(A)
 2. REVIEW LOAD CALCUALTION (ATTENTION TO A/C UNITS
 LOADS). NEC 220.82(B)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  