2022-11-22 13:13:021ST REVIEW FMC
 PERMIT: 22101226
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE EXPLAIN HOW THESE INTERIOR SPACES WILL BE
 CONDITIONED TO MEET THE HEATING REQUIREMENTS OF FMC
 309.1
  
 [BG] 309.1 SPACE-HEATING SYSTEMS. INTERIOR SPACES
 INTENDED FOR HUMAN OCCUPANCY SHALL BE PROVIDED WITH
 ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS CAPABLE OF
 MAINTAINING AN INDOOR TEMPERATURE OF NOT LESS THAN
 68???F (20???C) AT A POINT 3 FEET (914 MM) ABOVE FLOOR
 ON THE DESIGN HEATING DAY. THE INSTALLATION OF PORTABLE
 SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE
 WITH THIS SECTION.
 EXCEPTIONS:
 1. INTERIOR SPACES WHERE THE PRIMARY PURPOSE IS NOT
 ASSOCIATED WITH HUMAN COMFORT.
 2. GROUP F, H, S AND U OCCUPANCIES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  