Plan Review Notes For Permit 22101213 |
Permit Number |
22101213 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-11-10 11:45:52 | 2ND REVIEW FMC | | PERMIT: 22101213 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE THE COMPLETE DESIGN INCLUDING THE SIZES OF | | THE MECHANICAL UNITS. AHU-1 AND AHU-2 HAVE BEEN | | REVERSED IN THE LOCATIONS OF THE HOUSE. AHU-2 IS NOW | | SERVING THE GUEST BEDROOMS AND AHU-1 IS NOW SERVING THE | | REST OF THE HOUSE. THIS DRAWING DOES NOT INDICATE THE | | SIZES OF THE UNITS. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|