2022-11-29 12:35:14 | 1ST BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE GUEST |
| HOUSE. ALL PLANS MAY REMAIN UNDER THE MAIN DWELLING |
| UNIT (22101205). PERMITS SHALL TRAVEL TOGETHER. |
| |
| 1. REFERENCE PLAN PAGE 1 OF 1 FOR THE FOLLOWING: |
| 1A) CONSTRUCTION TYPE IS STATED AS TYPE IIIB. TYPE IIB |
| CONSTRUCTION SHALL BE DESIGNED PER THE FBC CHPT. 16 |
| AND/OR ASCE 7-16 WITH RATED EXTERIOR WALLS. |
| CONSTRUCTION TYPE FOR THIS STRUCTURE IS TYPE VB AND CAN |
| BE DESIGNED PER FBC RESIDENTIAL CHAPTER 3. |
| 1B) OCCUPANCY IS STATED AS GROUP VB. THE OCCUPANCY |
| CLASSIFICATION PER FBC CHPT 3, SECTION 310 IS |
| RESIDENTIAL GROUP R-3. |
| 1C) NEW DECK IS MISSING FROM THE SCOPE OF WORK (SOW). |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 2. PROVIDE AN EXISTING FLOOR PLAN FOR BOTH STRUCTURES. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 3. PROVIDE REQUIRED DEMENSIONS ON PROPOSED FLOOR PLANS. |
| VERIFY CLEARANCES IN BATHROOMS. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 4.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE |
| SURVEY. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 5. PROVIDE A SITE PLAN.... |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE |
| AND INCLUDED BOUNDARY LINE SURVEY. |
| |
| 6. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| |
| 7.PROVIDE SMOKE ALARMS. |
| FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| BUILDING. |
| SMOKE ALARMS |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |