2022-12-07 14:01:53 | PLAN REVIEW COMMENTS FOR REVISION 22101149 TO MASTER |
| PERMIT 14011176 |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2010) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. |
| ON THE DATE (1/21/2014) THE PERMIT WAS APPLIED FOR, THE |
| FLOOD MAP THAT WAS IN EFFECT HAD THIS PROPERTY AS AN A5 |
| FLOOD ZONE WITH A BFE OF 7' NGVD 1929. THE CITY OF WEST |
| PALM BEACH HAD A 6" FREEBOARD REQUIREMENTS AT THAT |
| TIME. THEREFORE, THE LOWEST FLOOR ELEVATION FOR THE |
| BUILDING AND EQUIPMENT SERVICING THE BUILDING WAS 7.5' |
| NGVD. THIS IS THE DESIGN FLOOD ELEVATION OR DFE. |
| |
| 1) SPECIFY THE FINISH FLOOR ELEVATION FOR THE GROUND |
| FLOOR ON THE FLOOR PLAN IN NGVD 1929. FBC 107.2.1 |
| |
| 2) THE FLOOD VENT CALCULATIONS FOR THE GARAGE AREA DO |
| NOT APPEAR TO BE CORRECT. THE GARAGE IS 23' 4" X 47' 4" |
| WHICH IS 1104.42 SQFT. THE STORAGE ROOM IS 21' 7" X 23' |
| 4" WHICH EQUALS 503.60 SQFT. BOTH OF THESE AREAS ARE |
| BELOW THE REQUIRED DFE OF 7.5' NGVD AND ARE ALLOWED TO |
| BE DESIGNED FOR WET FLOOD PROOFING WITH FLOOD VENTS TO |
| ALLOW FLOOD WATER TO ENTER AND LEAVE THE BUILDING. |
| NON-ENGINEERED FLOOD OPENINGS ARE REQUIRED TO MEET THE |
| PRESCRIPTIVE REQUIREMENT TO PROVIDE 1 SQUARE INCH OF |
| NET OPEN AREA FOR EACH SQUARE FOOT OF ENCLOSED AREA, |
| WHERE THE ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF |
| THE ENCLOSURE WALLS. ENGINEERED FLOOD OPENINGS HAVE AN |
| EVALUATION REPORT THAT SPECIFY THE AMOUNT OF COVERAGE |
| THAT THEY WILL PROVIDE. THE FLOOD VENTS ARE REQUIRED TO |
| BE IN AT LEAST TWO DIFFERENT WALLS. ALSO THE AREA UNDER |
| THE STAIRS IS REQUIRED TO BE OPEN OR HAVE FLOOD |
| OPENINGS. SEE FEMA, NFIP TECHNICAL BULLETIN 1 FOR |
| ADDITIONAL INFORMATION. SHOW COMPLIANCE. FBC-R322 |
| |
| 3) IN ADDITION TO THE FLOOD OPENINGS, THERE IS A |
| REQUIREMENT THAT ALL MATERIALS THAT ARE BELOW THE DFE |
| SHALL BE RESISTANT TO DAMAGE FROM FLOOD WATERS. SHOW |
| COMPLIANCE. FBC-R322 |
| |
| 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |