Plan Review Notes
Plan Review Notes For Permit 22101138
Permit Number 22101138
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2023-06-14 14:52:43THE PREVIOUS COMMENTS FROM FIRE WERE NOT SPECIFICAALY
 ADDRESS AND HAVE BEED RESUBMITTED BELOW:
  
  
 *******************************************************
 *******************************************************
 ***********
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE REPLACEMENT OF
 EXISTING MATERIAL; HOWEVER, THERE IS NO SITE PLAN
 SHOWING THE LOCATION OF THE EXISTING STRUCTURE.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDEA SITE PLAN
 INDICATING WHERE THE PROPOSED REPLACEMENT STRUCTURE IS
 LOCATED
  
  
 2) PLEASE PROVIDE DETAILS IF THERE IS ANY ELECTRICAL
 WORK IS PROPOSED OR IS BEING SYBMITTED UNDER SEPARATE
 PERMIT.
  
  
  
 3) PLEASE PROVIDE DETAILS IF THERE IS ANY EXITING
 THROUGH THIS AREA AND IF THE WORK WILL BE DONE WHILE
 THE OCCUPANCY IS OPEN.
  
 IF OPEN AND EXTING OCCURS THROUGH THIS AREA, PLEASE
 PROVIDE DETAILS FOR ALTERNATIVE EXITS/EXIT ROUTING.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  