Plan Review Notes
Plan Review Notes For Permit 22101116
Permit Number 22101116
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2023-01-19 10:12:06FIRE PROVISO COMMENTS:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF INSPECTION BY A FIRE DEPARTMENT
 INSPECTOR. FAILURE TO FOLLOW THESE PROVISO COMMENTS
 WILL RESULT IN A FAILED FIRE INSPECTION.
  
 INSTALLATION, TESTING AND INSPECTION SHALL BE PER THE
 REQUIREMENTS OF NFPA 24, STANDARD FOR THE INSTALLATION
 OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES.
 THIS SHALL INCLUDE BUT NOT LIMITED TO WITNESSING THE
 TORQUE OF BOLTED JOINTS TO THE MANUFACTURER???S
 SPECIFICATIONS, PROPER COATING OF BOLTED JOINTS AND
 HYDROSTATIC TESTING.
  
 DO NOT COVER OVER ANY JOINTS PRIOR TO FIRE DEPARTMENT
 INSPECTION.
  