Plan Review Notes For Permit 22101116 |
Permit Number |
22101116 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-12-16 07:27:06 | FIRE PROVISO COMMENTS: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF INSPECTION BY A FIRE DEPARTMENT | | INSPECTOR. FAILURE TO FOLLOW THESE PROVISO COMMENTS | | WILL RESULT IN A FAILED FIRE INSPECTION. | | | | INSTALLATION, TESTING AND INSPECTION SHALL BE PER THE | | REQUIREMENTS OF NFPA 24, STANDARD FOR THE INSTALLATION | | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES. | | THIS SHALL INCLUDE BUT NOT LIMITED TO WITNESSING THE | | TORQUE OF BOLTED JOINTS SO THE MANUFACTURER | | SPECIFICATIONS, PROPER COATING OF BOLTED JOINTS AND | | HYDROSTATIC TESTING. | | | | DO NOT COVER OVER ANY JOINTS PRIOR TO FIRE DEPARTMENT | | INSPECTION. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|