Plan Review Notes
Plan Review Notes For Permit 22100972
Permit Number 22100972
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-11-03 16:27:471. APPLIED PERMIT SHOULD BE A SIGN PERMIT, NOT A
 COMMERICIAL REVISION.
  
 2. PLEASE CLEAN UP PAGE 3, THE WEST ELEVATION SHEET.
 THE LABELS AND DIMENSIONS FOR "SIGN BAND" ON THE
 CONTEXT VIEW OR ELEVATION DRAWING ARE NOT APPLICABLE,
 AS THIS SIGN IS CONSIDERED A BUILDING IDENTITY SIGN.
 PLEASE LABEL ACCORDINGLY.
 DUE TO SCALE OF THE BUILDING, MAXIMUM SQUAREFOOTAGE OF
 IDENTITY SIGN IS 200 SF, PROPOSED 145 SF FALLS WITHIN
 THIS CATEGORY. PLEASE CLARIFY THAT THIS IDENTITY SIGN
 IS ONLY IN 1 LOCATION ON THE WESTERN FACADE, THERE ARE
 NOT MULTIPLE SIGNS.
  
 3. PAGE 3 AND 4 SHOWS EXPOSED CONDUIT, THIS IS
 PROHIBITED PER THE CODE.
  
  
  
  
 FOR REFERENCE:
  
 SEC.94-110
 EXPOSED CONDUIT OR ELECTRICAL WIRING IS PROHIBITED.
 EXPOSED RACEWAYS, TRANSFORMERS, BALLASTS, AND
 ELECTRICAL WIRING ARE PROHIBITED.
  
 1. UP TO TWO BUILDING IDENTITY SIGNS, WITH THE SAME
 IDENTITY, SHALL BE ALLOWED ON BUILDINGS THREE OR MORE
 STORIES IN HEIGHT. ONLY ONE BUILDING IDENTITY SIGN
 SHALL BE ALLOWED PER FACADE. SUCH SIGNS SHALL NOT
 EXCEED A TOTAL SIGN FACE OF 100 SQUARE FEET EACH. FOR
 BUILDINGS TEN STORIES OR TALLER, THE MAXIMUM SIGN FACE
 SHALL NOT EXCEED 200 SQUARE FEET EACH. BUILDING
 IDENTITY SIGNS MAY BE COMPRISED OF INTERNALLY
 ILLUMINATED INDIVIDUAL LETTERS AND PRIMARY LOGOS, BUT
 NOT INTERNALLY ILLUMINATED BOX SIGNS. INDIVIDUAL
 LETTERS SHALL BE ATTACHED DIRECTLY TO THE BUILDING
 FACADE. IN THOSE CASES WHERE THE INDIVIDUAL LETTERS
 CANNOT BE ATTACHED DIRECTLY TO THE BUILDING FACADE, A
 SUPPORT BACK PANEL MAY BE ALLOWED, BUT SUCH PANEL SHALL
 NOT BE INTERNALLY ILLUMINATED.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426