Plan Review Notes
Plan Review Notes For Permit 22100953
Permit Number 22100953
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2022-11-28 10:38:111ST NFIP PLAN REVIEW
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE:
 CORRECTIONS REQUIRED
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 1. ATTACH A COPY OF THE ICC-ES REPORT FOR THE SMART
 VENTS.
  
 2. LINE C2E) LOWEST ELEVATION OF MACHINERY... 7.1FT
 NAVD. MINIMUM ELEVATION SHALL BE 8'0"NAVD.
  
 3. LINE A8 SHOULD BE FILLED OUT IN PLACE OF A9 (THE
 GARAGE IS THE BUILDING - NOT AN ATTACHED GARAGE)
  
 4. LINE B9 = SHOULD BE 6 (THE BUILDING IN QUESTION IS
 IN AE 6)
  
 5. LINE C2(D) = SHOULD BE N/A ITS NOT THE ATTACHED
 GARAGE IT IS THE BUILDING.
  
 6. SECTION D = THE BOX THAT SAYS CHECK HERE IF
 ATTACHMENTS SHOULD BE CHECKED (THE SMART VENT DOCUMENTS
 WOULD BE THE ATTACHMENTS).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  