2023-01-09 11:16:07RESIDENTIAL (R2) THIRD REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100952
 1801 N FLAGLER DR # 309
  
 1-FLOORING SOUND INSULATION MATERIAL:
  
 ORIGINAL COMMENT:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT.
  
 ORIGINAL COMMENT:
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT.
  
 ORIGINAL COMMENT:
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  