Plan Review Notes
Plan Review Notes For Permit 22100890
Permit Number 22100890
Review Stop M
Sequence Number 5
Notes
Date Text
2023-03-14 10:05:555TH REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 1) MAIN ENTRY LOBBIES: 349 SQ FT 349/1000 = .349; .349
 X 10 OCCUPANT DENSITY = 3.49, ROUND UP TO 4; 4 X 5
 CFM/PERSON = 20 CFMS REQUIRED FOR THE OCCUPANTS; 349 SQ
 FT X .06 CFM/SQ.FT. = 20.94 CFM FOR THE SPACE; 20 + 21
 = 41 CFM REQUIRED FOR THE MAIN ENTRY LOBBY.
  
 2) MULTI-USE ASSEMBLY: 4,976 SQ. FT., 4976/1000 = 4.976
 OCCUPANTS ROUND UP; 5 X 100 = 500; 500 X 7.5 = 3750 CFM
 FOR OCCUPANTS; 4976 X .06 = 298.56 ROUND UP; 3750 + 299
 = 4049 CFM REQUIRED FOR MULTI-USE ASSEMBLY.
  
 3) DINING: 400 SQ. FT., 400/ 1000 = .4; .4 X 70 = 28
 OCCUPANTS; 28 X 7.5 = 210 CFM REQUIRED FOR THE
 OCCUPANTS; 400 X .18 = 72 CFM FOR THE SPACE. 210 + 72 =
 282 CFM REQUIRED FOR DINING
  
 4) THE TOTAL OUTDOOR AIR REQUIRED FOR THIS CHANGE OF
 USE IS 4,414 CFMS.
  
 4414/ 3 = 1471 CFM OF O.A. PER UNIT
 TYPICAL O.D. SUPPLIED FROM A 5-TON UNIT IS 350 CFM: SO,
 700 CFMS X 3 10-TON UNIT = 2100 CFM???S OF OUTDOOR AIR.
  
 PLEASE SHOW THAT THE EXISTING UNITS WILL BE SIZED TO
 BRING IN THE REQUIRED OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  