Date |
Text |
2023-03-14 10:05:55 | 5TH REVIEW FMC |
| PERMIT: 22100890 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 1) MAIN ENTRY LOBBIES: 349 SQ FT 349/1000 = .349; .349 |
| X 10 OCCUPANT DENSITY = 3.49, ROUND UP TO 4; 4 X 5 |
| CFM/PERSON = 20 CFMS REQUIRED FOR THE OCCUPANTS; 349 SQ |
| FT X .06 CFM/SQ.FT. = 20.94 CFM FOR THE SPACE; 20 + 21 |
| = 41 CFM REQUIRED FOR THE MAIN ENTRY LOBBY. |
| |
| 2) MULTI-USE ASSEMBLY: 4,976 SQ. FT., 4976/1000 = 4.976 |
| OCCUPANTS ROUND UP; 5 X 100 = 500; 500 X 7.5 = 3750 CFM |
| FOR OCCUPANTS; 4976 X .06 = 298.56 ROUND UP; 3750 + 299 |
| = 4049 CFM REQUIRED FOR MULTI-USE ASSEMBLY. |
| |
| 3) DINING: 400 SQ. FT., 400/ 1000 = .4; .4 X 70 = 28 |
| OCCUPANTS; 28 X 7.5 = 210 CFM REQUIRED FOR THE |
| OCCUPANTS; 400 X .18 = 72 CFM FOR THE SPACE. 210 + 72 = |
| 282 CFM REQUIRED FOR DINING |
| |
| 4) THE TOTAL OUTDOOR AIR REQUIRED FOR THIS CHANGE OF |
| USE IS 4,414 CFMS. |
| |
| 4414/ 3 = 1471 CFM OF O.A. PER UNIT |
| TYPICAL O.D. SUPPLIED FROM A 5-TON UNIT IS 350 CFM: SO, |
| 700 CFMS X 3 10-TON UNIT = 2100 CFM???S OF OUTDOOR AIR. |
| |
| PLEASE SHOW THAT THE EXISTING UNITS WILL BE SIZED TO |
| BRING IN THE REQUIRED OUTDOOR AIR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |