Plan Review Notes
Plan Review Notes For Permit 22100890
Permit Number 22100890
Review Stop M
Sequence Number 4
Notes
Date Text
2023-03-07 13:43:004TH REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WITH THIS CHANGE OF USE GOING FROM EDUCATIONAL TO AN
 ASSEMBLY OCCUPANCY THE OUTDOOR AIR CALCULATIONS MUST BE
 SUBMITTED TO SHOW THAT THE MECHANICAL SYSTEMS CAN
 HANDLE THE EXTRA LOAD OF MORE PEOPLE BEING ABLE TO
 OCCUPY THE SAME SPACE. PLEASE SUBMIT THE REQUIRED
 OUTDOOR AIR CALCULATIONS FOR THIS USE OF SPACE. THE
 OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES
 THE USE FROM TABLE 403.3.1.1 MUST BE USED FOR THE
 CALCULATIONS. THE OCCUPANT DENSITY FOR THIS OCCUPANCY
 CLASSIFICATION MUST BE USED TO FIND THE MINIMUM
 REQUIRED OCCUPANTS FOR THIS CALCULATION. FMC 403.3.1.1
 AND TABLE 403.3.1.1.
  
 2) THE DESIGNER MUST SHOW THAT THE MECHANICAL SYSTEMS
 THAT ARE EXISTING ARE SIZED CORRECTLY FOR THIS CHANGE
 OF USE. FEC C403.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  