2023-03-07 13:43:00 | 4TH REVIEW FMC |
| PERMIT: 22100890 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) WITH THIS CHANGE OF USE GOING FROM EDUCATIONAL TO AN |
| ASSEMBLY OCCUPANCY THE OUTDOOR AIR CALCULATIONS MUST BE |
| SUBMITTED TO SHOW THAT THE MECHANICAL SYSTEMS CAN |
| HANDLE THE EXTRA LOAD OF MORE PEOPLE BEING ABLE TO |
| OCCUPY THE SAME SPACE. PLEASE SUBMIT THE REQUIRED |
| OUTDOOR AIR CALCULATIONS FOR THIS USE OF SPACE. THE |
| OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES |
| THE USE FROM TABLE 403.3.1.1 MUST BE USED FOR THE |
| CALCULATIONS. THE OCCUPANT DENSITY FOR THIS OCCUPANCY |
| CLASSIFICATION MUST BE USED TO FIND THE MINIMUM |
| REQUIRED OCCUPANTS FOR THIS CALCULATION. FMC 403.3.1.1 |
| AND TABLE 403.3.1.1. |
| |
| 2) THE DESIGNER MUST SHOW THAT THE MECHANICAL SYSTEMS |
| THAT ARE EXISTING ARE SIZED CORRECTLY FOR THIS CHANGE |
| OF USE. FEC C403.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |