2023-02-14 14:17:373RD REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS CHANGE OF USE DOES REQUIRE THE SPACE TO MEET
 THE OUTDOOR AIR REQUIREMENTS FOR THIS NEW OCCUPANCY.
 PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR THIS
 NEW CHANGE OF USE. THE OUTDOOR AIR CALCULATIONS SHALL
 BE DESIGNED FROM THE OCCUPANCY CLASSIFICATION AND
 OCCUPANT DENSITY OF FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  