| PLUMBING COMMENTS: DENIED |
| |
| |
| |
| 1. COMPLIED |
| |
| 2. PARTIALLY COMPLIED: BASED ON PLANS FROM PREVIOUS |
| TENANT (SEE CLOSED PERMIT #02060943), IT APPEARS THERE |
| ARE TO BE NO PLUMBING CHANGES FROM THE ORIGINAL |
| OCCUPANCY. PLEASE CLARIFY. PLEASE PROVIDE LOCATION OF |
| EXISTING WATER HEATER. WPB FBC 107.3.5.1.3 |
| |
| 3. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PLEASE |
| PROVIDE NEW OCCUPANCY DESIGNATION AS SPELLED OUT IN FBC |
| SECTION 302 AND PROVIDE OCCUPANCY LOAD FOR DESIGNATED |
| CLASSIFICATION AS SPELLED OUT IN FBC SECTION 1004 SO |
| THAT A DETERMINATION OF MINIMUM PLUMBING FIXTURE |
| REQUIREMENTS CAN BE DETERMINED IN ACCORDANCE WITH FBC |
| PL SECTION 403; PROVIDE PLUMBING FIXTURE SCHEDULE |
| SHOWING MINIMUM FIXTURE REQUIREMENTS FOR THE OCCUPANCY |
| IN ACCORDANCE WITH FBC PL TABLE 403.1 AND THE ACTUAL |
| FIXTURES PROVIDED. |
| TO BE CLEAR, PLEASE INDICATE BASED ON NEW OCCUPANCY AND |
| FBC PL TABLE 403.1, THE MINIMUM PLUMBING FIXTURE |
| REQUIREMENTS INCLUDING QUANTITIES (INCLUDE POTTY PARITY |
| FBC PL 403.1.3) AND THE ACTUAL FIXTURES (QUANTITY) |
| PROVIDED. FBC EX 1010.1 |
| |
| 4. SECOND REQUEST: A REVIEW OF MINIMUM PLUMBING FIXTURE |
| REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE |
| PLUMBING REVIEW PROCESS (SEE FBC PL 404.1) BUT IS |
| TYPICALLY ADDRESSED ON THE ARCHITECTURAL PLANS. ANY |
| COMMENTS CONCERNING THESE REQUIREMENTS MUST BE |
| SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL; PROVIDE PLAN AND ELEVATION DETAILS FOR |
| ACCESSIBLE TOILET ROOM FACILITIES, DRINKING FOUNTAIN(S) |
| AND ACCESSIBLE SINKS. COMPLY WITH FBC ACC CHAPTERS 2, 3 |
| AND 6. |
| |
| ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A |
| CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| THE PROVISIONS OF THE FLORIDA ACCESSIBILITY CODE 2020 |
| 7TH EDITION PER FBC EX 1006.1 |
| |
| ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL |
| OR PARTITION TO THE REAR AND TO ONE SIDE. THE |
| CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| PARTITION PER FBC ACC 604.2 |
| ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| THE REAR WALL PER FBC ACC 604.3.1 |
| ***C) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER |
| CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED |
| WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL |
| PER FBC ACC 604.3.1 AND 604.8.1.1. |
| ***E) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| WALL PER FBC ACC 604.5.1 |
| ***F) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| ***G) FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| SIDE OF THE WATER CLOSET PER FBC ACC 604.6 |
| ***H) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL |
| COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 |
| INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED |
| BEHIND GRAB BARS. |
| ***J) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE |
| FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 |
| INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE |
| SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED |
| POSITION PER FBC ACC 604.4. |
| ***K) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED |
| IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 |
| INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE |
| TOP (NOT THE CENTER) OF THE GRIPPING SURFACE. |
| ***L) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG |
| TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP |
| MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM |
| TO THE BACK OF THE FIXTURE PER FBC ACC 605.2. |
| ***M) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| REQUIRED BY FBC ACC 306.2 AND 306.3 |
| ***N) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5 |
| PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 |
| PER FBC ACC 212.3 |
| ***O) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| CONTACT. |
| ***P) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| ACC 603.3. |
| TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS |
| TO THE REFLECTING SURFACE OF THE MIRROR. |
| ***Q) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 |
| OR 304.3.2. |
| ***R) DRINKING FOUNTAINS SHALL HAVE A CLEAR FLOOR OR |
| GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC |
| ACC 602.2. |
| ***S) SPOUT OUTLETS FOR ACCESSIBLE DRINKING FOUNTAINS |
| SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND PER FBC ACC 602.4. |
| ***T) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND PER FBC ACC 602.7. |
| |
| |
| 5. N/A |
| |
| |
| END OF COMMENTS. |
| |
| |