2023-01-18 16:47:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22100890 7719 S DIXIE HWY
  
 2ND REVIEW
 ELECTRONIC SIGNATURES ARE NOT VALID
  
 PLUMBING COMMENTS: DENIED
  
  
  
 1. COMPLIED
  
 2. PARTIALLY COMPLIED: BASED ON PLANS FROM PREVIOUS
 TENANT (SEE CLOSED PERMIT #02060943), IT APPEARS THERE
 ARE TO BE NO PLUMBING CHANGES FROM THE ORIGINAL
 OCCUPANCY. PLEASE CLARIFY. PLEASE PROVIDE LOCATION OF
 EXISTING WATER HEATER. WPB FBC 107.3.5.1.3
  
 3. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PLEASE
 PROVIDE NEW OCCUPANCY DESIGNATION AS SPELLED OUT IN FBC
 SECTION 302 AND PROVIDE OCCUPANCY LOAD FOR DESIGNATED
 CLASSIFICATION AS SPELLED OUT IN FBC SECTION 1004 SO
 THAT A DETERMINATION OF MINIMUM PLUMBING FIXTURE
 REQUIREMENTS CAN BE DETERMINED IN ACCORDANCE WITH FBC
 PL SECTION 403; PROVIDE PLUMBING FIXTURE SCHEDULE
 SHOWING MINIMUM FIXTURE REQUIREMENTS FOR THE OCCUPANCY
 IN ACCORDANCE WITH FBC PL TABLE 403.1 AND THE ACTUAL
 FIXTURES PROVIDED.
 TO BE CLEAR, PLEASE INDICATE BASED ON NEW OCCUPANCY AND
 FBC PL TABLE 403.1, THE MINIMUM PLUMBING FIXTURE
 REQUIREMENTS INCLUDING QUANTITIES (INCLUDE POTTY PARITY
 FBC PL 403.1.3) AND THE ACTUAL FIXTURES (QUANTITY)
 PROVIDED. FBC EX 1010.1
  
 4. SECOND REQUEST: A REVIEW OF MINIMUM PLUMBING FIXTURE
 REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE
 PLUMBING REVIEW PROCESS (SEE FBC PL 404.1) BUT IS
 TYPICALLY ADDRESSED ON THE ARCHITECTURAL PLANS. ANY
 COMMENTS CONCERNING THESE REQUIREMENTS MUST BE
 SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL; PROVIDE PLAN AND ELEVATION DETAILS FOR
 ACCESSIBLE TOILET ROOM FACILITIES, DRINKING FOUNTAIN(S)
 AND ACCESSIBLE SINKS. COMPLY WITH FBC ACC CHAPTERS 2, 3
 AND 6.
  
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA ACCESSIBILITY CODE 2020
 7TH EDITION PER FBC EX 1006.1
  
 ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL PER FBC ACC 604.3.1
 ***C) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***E) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***F) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***G) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***H) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***J) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 ***K) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***L) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP
 MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
 TO THE BACK OF THE FIXTURE PER FBC ACC 605.2.
 ***M) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ***N) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3
 ***O) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***P) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR.
 ***Q) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2.
 ***R) DRINKING FOUNTAINS SHALL HAVE A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC
 ACC 602.2.
 ***S) SPOUT OUTLETS FOR ACCESSIBLE DRINKING FOUNTAINS
 SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 602.4.
 ***T) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 602.7.
  
  
 5. N/A
  
  
 END OF COMMENTS.
  
  