Plan Review Notes For Permit 22100890 |
Permit Number |
22100890 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-01-19 11:30:41 | 1ST REVIEW FMC | | PERMIT: 22100890 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) ADDRESS THE PREVIOUS MECHANICAL COMMENTS. | | | | 1) PLEASE PROVIDE THE MECHANICAL DESIGN FOR THE CURRENT | | PERMITTED USE OF THIS TENANT SPACE ALONG WITH A DRAWING | | SHOWING THE PURPOSED USE. THE DRAWING SUBMITTED DOES | | NOT SHOW MUCH INFORMATION FOR THE MECHANICAL DESIGN. | | PROVIDE A COMPLETE OUTDOOR AIR CALCULATION SHOWING EACH | | USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND | | TABLE 403.3.1.1 | | | | 2) PROVIDE MORE INFORMATION ABOUT THE STAGE ON THE | | DRAWING. FBC 410.3.7, 410.3.7.2 | | | | 3) PROVIDE MORE INFORMATION ABOUT THE KITCHEN AREA ON | | THE DRAWING. FMC 507 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|