Plan Review Notes For Permit 22100890 |
Permit Number |
22100890 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-01-25 10:35:31 | FIRE REVIEW COMMENTS: | | | | (1) THE OCCUPANT LOAD CALCULATIONS ARE NOT CORRECT. THE | | DANCE FLOOR SHALL BE CALCULATED AT 7 SQ. FT. PER PERSON | | NET. NFPA 101, LIFE SAFETY CODE, 7.3.1.2 | | | | (2) PROVIDE A TOTAL OCCUPANT LOAD CALCULATION FOR THE | | ENTIRE SPACE. NFPA 101, LIFE SAFETY CODE, 12.1.7 | | | | (3) PROVIDE EXIT DOOR HARDWARE DETAILS INCLUDING | | LOCKING DEVICES. NFPA 101, LIFE SAFETY CODE, 12.2.2 | | | | (4) PROVIDE THE AISLE WIDTH SERVING SEATING AT TABLES. | | NFPA 101, LIFE SAFETY CODE 12.2.5.8 | | | | | | (5) ANY CHANGES, ADDITIONS, MODIFICATIONS, ETC. TO ANY | | LIFE SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM) | | SHALL BE PERFORMED BY PROPERLY LICENSED CONTRACTORS | | UNDER SEPARATE PERMITS AND SHOP DRAWINGS. A REVIEW OF | | LIFE SAFETY FEATURES MAY NEED TO BE CONDUCTED. NFPA | | 101, LIFE SAFETY CODE, 12.4.1.3.3 | | | | (6) PROVIDE DETAILS ON INTERIOR FINISHES. NFPA 101, | | LIFE SAFETY CODE, 12.3.3 | | | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|