2022-11-02 12:02:05 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22100890 7719 S DIXIE HWY |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. THE FLOOR PLAN WAS NOT DESIGNED BY EITHER AN |
| ENGINEER OR ARCHITECT. CERTIFICATION BY CONTRACTOR. THE |
| CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET OF |
| PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| PLANS DRAWN. WPB FBC 107.3.4.3 CERTIFICATION BY |
| CONTRACTOR. |
| PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER |
| PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| ISSUANCE OF A PERMIT. |
| PER WPB FBC 107.2.1, PLEASE REFERENCE ON THE PLANS THE |
| CODES THAT APPLY (SEE LIST ABOVE) |
| |
| 2. PROVIDE A FULL SCOPE OF WORK AND AS APPLICABLE, AN |
| EXISTING/DEMOLITION PLUMBING FLOOR PLAN WITH ALL |
| EXISTING PLUMBING FIXTURES AND EQUIPMENT INCLUDING |
| WATER HEATERS AND A PROPOSED PLUMBING FLOOR PLAN WITH |
| ALL PLUMBING FIXTURES AND EQUIPMENT INCLUDING WATER |
| HEATERS. PROVIDE AS APPLICABLE, PLUMBING PLAN VIEW TO |
| INCLUDE WATER AND SANITARY PIPING, PLUMBING FIXTURES, |
| NEW OR EXISTING WATER SERVICE BACKFLOW PREVENTER AND |
| EQUIPMENT INCLUDING WATER HEATERS AND PLUMBING |
| WATER/SANITARY RISER DIAGRAMS AND DETAILS. ADDRESS AS |
| APPLICABLE, THE REQUIREMENTS OF WPB FBC 107.3.5.1.3 |
| BELOW. |
| 1. MINIMUM PLUMBING FACILITIES |
| 2. FIXTURE REQUIREMENTS |
| 3. WATER SUPPLY PIPING |
| 4. SANITARY DRAINAGE |
| 5. WATER HEATERS |
| 6. VENTS |
| 7. ROOF DRAINAGE |
| 8. BACKFLOW PREVENTION |
| 9. IRRIGATION |
| 10. LOCATION OF WATER SUPPLY LINE |
| 11. GREASE TRAPS |
| 12. ENVIRONMENTAL REQUIREMENTS |
| 13. PLUMBING RISER (SANITARY AND WATER) |
| 14. DESIGN FLOOD ELEVATION |
| |
| 3. PER WPB FBC 107.2.1, PLEASE PROVIDE NEW OCCUPANCY |
| DESIGNATION AS SPELLED OUT IN FBC SECTION 302 AND |
| PROVIDE OCCUPANCY LOAD FOR DESIGNATED CLASSIFICATION AS |
| SPELLED OUT IN FBC SECTION 1004 SO THAT A DETERMINATION |
| OF MINIMUM PLUMBING FIXTURE REQUIREMENTS CAN BE |
| DETERMINED IN ACCORDANCE WITH FBC PL SECTION 403; |
| PROVIDE PLUMBING FIXTURE SCHEDULE SHOWING MINIMUM |
| FIXTURE REQUIREMENTS FOR THE OCCUPANCY IN ACCORDANCE |
| WITH FBC PL TABLE 403.1 AND THE ACTUAL FIXTURES |
| PROVIDED. |
| |
| 4. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| PRIOR TO A PLUMBING REVIEW APPROVAL; PROVIDE PLAN AND |
| ELEVATION DETAILS FOR ACCESSIBLE TOILET ROOM |
| FACILITIES, DRINKING FOUNTAIN(S) AND ACCESSIBLE SINKS. |
| COMPLY WITH FBC ACC CHAPTERS 2, 3 AND 6. |
| |
| 5. VALUE OF JOB MAY NEED TO BE ADJUSTED BASED UPON A |
| PROPOSED SCOPE OF WORK AND RESUBMITTALS. PROVIDE AN |
| ACCURATE VALUATION OF ALL WORK AND COST. WPB FBC 109.3 |
| BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE |
| BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL (1) CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| |
| END OF COMMENTS. |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE FIRST REVIEW. |
| |
| |