2022-12-02 06:19:402ND REVIEW FMC
 PERMIT: 22100873
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2-1 INDICATES A NEW VAV-2 FOR THE NOW CLOUDED
 AREA FOR THIS REVISION. SHEET M6-1 DOES NOT SHOW A NEW
 VAV-2, IT DOES SHOW A CLOUDED MINI SPLIT SYSTEM AHU-1.
 PLEASE HELP THIS REVIEWER UNDERSTAND THIS REVISION. IF
 THERE IS A NEW AHU-1 INDICATE ON M2-1 THE LOCATION OF
 AHU-1 AND ALSO PROVIDE A DRAWING INDICATING WHERE THE
 NEW CU-1 IS LOCATED AND THE MOUNTING DETAILS. FBC
 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  