Plan Review Notes
Plan Review Notes For Permit 22100872
Permit Number 22100872
Review Stop P
Sequence Number 4
Notes
Date Text
2023-03-14 08:45:484TH PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1 - THE NOTE ADDED DETAILING THE
 MODEL NUMBER FOR THE WATER HEATER DOES NOT INDICATE
 THAT THE MIXING VALVE IS PRESENT. I LOOKED UP THE WATER
 HEATER AND THE DETAILS ONLINE DO NOT SHOW THAT THIS
 WATER HEATER HAS EITHER ASSE 1017 OR ASSE 1070
 COMPLIANCE. TO SUPPLY HOT WATER TO ANY FIXTURE, YOU
 MUST HAVE AN ASSE 1017 MIXING DEVICE. AND TO SUPPLY
 TEMPERED WATER TO A PUBLIC HANDWASHING STATION YOU MUST
 HAVE AN ASSE 1070 MIXING DEVICE.
  
 2. 2017 WPB AMENDS 107.2.1 - AFTER DETAILING A
 POINT-OF-USE WATER HEATER, YOU WOULD NEED TO ELEMINATE
 THE WATER HEATER DIAGRAM FOR CONSITENCY.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  