2023-03-14 08:45:48 | 4TH PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FPC 607.1.1 - THE NOTE ADDED DETAILING THE |
| MODEL NUMBER FOR THE WATER HEATER DOES NOT INDICATE |
| THAT THE MIXING VALVE IS PRESENT. I LOOKED UP THE WATER |
| HEATER AND THE DETAILS ONLINE DO NOT SHOW THAT THIS |
| WATER HEATER HAS EITHER ASSE 1017 OR ASSE 1070 |
| COMPLIANCE. TO SUPPLY HOT WATER TO ANY FIXTURE, YOU |
| MUST HAVE AN ASSE 1017 MIXING DEVICE. AND TO SUPPLY |
| TEMPERED WATER TO A PUBLIC HANDWASHING STATION YOU MUST |
| HAVE AN ASSE 1070 MIXING DEVICE. |
| |
| 2. 2017 WPB AMENDS 107.2.1 - AFTER DETAILING A |
| POINT-OF-USE WATER HEATER, YOU WOULD NEED TO ELEMINATE |
| THE WATER HEATER DIAGRAM FOR CONSITENCY. |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |