Date |
Text |
2023-02-21 09:28:10 | 2ND PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| COMMENTS WERE NOT ADDRESSED ON THE 1ST CYCLE. |
| |
| 1. DONE |
| |
| 2. DONE |
| |
| 3. THIS COMMENT NOT ADDRESSED - THE WATER HEATER DETAIL |
| AS WILL AS THE WATER RISER DIAGRAM SHOULD DETAIL AN |
| THERMOSTATIC MIXING DEVICE. AS NOTED, THIS IS IN |
| "ADDITION TO" THE REQUIREMENTS FOR PUBLIC HAND WASHING. |
| ALL HOT WATER SHALL GO THROUGH A LIMITING DEVICE AND |
| THE THERMOSTAT FOR THE WATER HEATER SHALL NEVER BE THE |
| LIMIT FOR HOT OR TEMPERED WATER DELIVERY. THIS DEVICE |
| SHALL BE INSTALLED AT THE HOT WATER SOURCE. |
| ESSENTIALLY, EVERY COMMERCIAL APPLICATION WILL HAVE A |
| THERMOSTATIC MIXING DEVICE INSTALLED AT THE WATER |
| HEATER. |
| 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS |
| SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT |
| SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER |
| DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE. |
| THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE |
| INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1. |
| THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC |
| HANDWASHING PROTECTION FOR TEMPERED WATER. |
| |
| 4. DONE |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |