2022-11-17 16:37:371ST REVIEW FMC
 PERMIT: 22100872
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE NEW OFFICE AND LAB ROOMS HAVE
 WALLS TO THE CEILING BASED ON THE NEW DUCT FOR THE
 OFFICE AREA. PLEASE SHOW HOW THE LAB WILL BE
 CONDITIONED AND ALSO SHOW THE RETURN AIR PATH BACK TO
 THE AHU FROM EACH ROOM. FMC 601.6
  
 2) THE OUTDOOR AIR CALCULATIONS DO NOT SHOW THE
 OCCUPANCY CLASSIFICATION, THERE SHOULD BE 3 DIFFERENT
 CLASSIFICATIONS: RETAIL SALES, OFFICE AND THE LAB
 SHOULD HAVE AN OCCUPANCY BASED ON THE BEST USE OF SPACE
 IN THE OCCUPANCY CLASSIFICATION COLUMN IN FMC TABLE
 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  