Plan Review Notes
Plan Review Notes For Permit 22100869
Permit Number 22100869
Review Stop B
Sequence Number 2
Notes
Date Text
2023-04-10 11:08:39OFFICE RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) CANNOT APPROVE DRAWINGS WITH THE "NOT FOR
 CONSTRUCTION" NOTE.
  
 2) DRAWING A8.00 - THE NOTES ADDED FOR THE TOILET SIDE
 GRAB BAR - (12" AND MIN. 42" BAR) ARE CONFUSING AND NOT
 NEEDED FOR AN AS NOTED (8" AND 4' BAR) . THE ADDED
 NOTES ALLOW FOR AN (8" AND 42" BAR) - WHICH WILL NOT
 MEET FBC 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR
 SHALL BE 42 INCHES (1065 MM) LONG MINIMUM, LOCATED 12
 INCHES (305 MM) MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES (1370 MM) MINIMUM FROM THE REAR
 WALL.
  
 3) DRAWINGS - CS INDEX, A2.00, A2.01, A8.00, A9.00 DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).